Instruction manual
7. DATA CONFIGURATION
IMCB14-E1
29
Continued from the previous page.
(Attribute RO: Read only R/W: Read and Write)
Address Name
Attrib-
ute
Data range or item description
Factor
y
set value
0FH Heat-side proportional band
(P) *4
R/W Temperature input: 1 (0.1) to span or
9999 (999.9) qC [qF]
Voltage/current inputs:
0.1 to 100.0 % of span
(ON/OFF action control when set to
0 or 0.0.)
Can not be set while the self-tuning
(ST) function is On
Temperature
input:
30 (30.0)
Voltage/
current
inputs:
3.0
10H Integral time (I) *4 R/W 1 to 3600 sec (0: PD control)
Can not be set while the self-tuning
(ST) function is On
240
11H Derivative time (D) *4 R/W 1 to 3600 sec (0: PI control)
Can not be set while the self-tuning
(ST) function is On
60
12H Anti-reset windup (ARW)
*4
R/W 1 to 100 % of heat-side proportional
band (0: Integral action OFF)
Can not be set while the self-tuning
(ST) function is On
100
13H Heat-side proportioning
cycle time
R/W 1 to 100 sec (0 can not be set.)
Can not be set if the control output
is current output.
*5
14H Cool-side proportional
band
R/W 1 to 1000% of heat-side proportional
band (0 can not be set.)
100
15H Deadband R/W Temperature input:
-10 to +10 qC [qF] or
-10.0 to +10.0 qC [qF]
Voltage/current inputs:
-10.0 to +10.0 % of span
0 or 0.0
16H Cool-side proportioning
cycle time
R/W 1 to 100 sec (0 can not be set.)
Can not be set if the control output
is current output.
*6
17H PV bias R/W -span to +span
However, temperature inputs:
-1999 to +1999 qC [qF] or
-199.9 to 999.9 qC [qF]
0 or 0.0
Continued on the next page.