7.3 Communication Data List
The communication data list summarizes data addresses (holding register numbers), names, attributes,
setting ranges and factory set values.
(Attribute RO: Read only R/W: Read and Write)
Address Name
Attrib-
ute
Data range or item description
Factor
y
set value
00H Measured value (PV) RO Within input range -
01H Current transformer input 1 RO 0.0 to 100.0 A -
02H Current transformer input 2
*1
RO 0.0 to 100.0 A -
03H Alarm 1 status RO 0: OFF 1: ON -
04H Alarm 2 status RO 0: OFF 1: ON -
05H Burnout RO 0: OFF 1: ON -
06H Set value (SV) R/W Within input range 0
07H Alarm 1 set value R/W Temperature input:
Process alarm, deviation alarm, SV
alarm:
-1999 to +9999 qC [qF] or
-199.9 to +999.9 qC [qF]
Temperature
input:
50 or 50.0
08H Alarm 2 set value Voltage/current inputs:
Deviation alarm: -span to +span
(Within 9999)
Process alarm, SV alarm:
Within input range
Voltage/
current
inputs:
5.0
09H Heater break alarm 1 R/W 0.0 to 100.0 A 0.0
0AH Heater break alarm 2 *2 R/W 0.0 to 100.0 A 0.0
0BH Control loop break alarm R/W 0. 1 to 200.0 min.
(0.0 can not be set.)
8.0
0CH LBA deadband R/W Temperature input:
0 to 9999 qC [qF]
Voltage/current inputs:
0 to 100 % of span
0
0DH Autotuning (AT) R/W 0: Autotuning (AT) end or
suspension
1: Autotuning (AT) start*
*After AT is completed, setting will
automatically change to 0
0
0EH Self-tuning (ST) *3 R/W 0: Self-tuning (ST) suspension
1: Self-tuning (ST) start
0
Continued on the next page.