Instruction manual

5. MODBUS PROTOCOL
IMCB14-E1
19
5.2 Function Code
z
Function code contents
Function code
(Hexadecimal)
Function Contents
03H
Read holding registers
Measured value (PV), alarm status, current
transformer input, etc.
06H
Preset single register
Set value (SV), alarm set value, PID constants,
PV bias, etc. (For each word)
08H
Diagnostics (loopback test)
Diagnostics (loopback test)
z
Message length of each function (Unit: byte)
Function code Function
Query message Response message
(Hexadecimal)
MinMaxMinMax
03H
Read holding registers 8 8 7 255
06H
Preset single register
8888
08H
Diagnostics (loopback test)
8888
5.3 Communication Mode
Signal transmission between the master and slaves is conducted in Remote Terminal Unit (RTU)
mode.
RTU mode
Items Contents
Data bit length 8 bit (Binary)
Start mark of message Unused
End mark of message Unused
Message length
See 5.2 Function Code
Data time interval 24 bit's time or less*
Error check CRC-16
* The data time intervals in one query message from the master must be 24 bit's time or less.
If the data time interval exceeds 24 bit's time, the slave regards the transmission as ended
and because the message format is incomplete, the slave does not respond.