4.6 Interval Time Setting
The interval time from 0 to 250 ms is set with numbers from 0 to 150. To shift the digit, press the
<R/S key. To change the number of the digit, press the UP or DOWN key.
Symbol Name Setting range Description
Factory set
value
Interval time set
value
0 to 150* Set the value to set the interval
time
5
InT
* 0 to 250 ms can be set by using 0 to 150.
Formula to calculate interval time and interval time set value
Interval time = Interval time set value
u
1.666 ms
Interval time set value = Interval time
y
1.666 ms
When the communication parameter is changed, turn the power on and off again to refresh and
make the new value effective.
All interval times must be stored by pressing the SET key. If changes are made and the SET
key is not pressed within one minute, the display will automatically return to the PV/SV
display mode and the interval time will return to the value prior to set change.
Setting procedure
Example: Setting the interval time to 250 ms.
1. Go to the communication setting mode so that slave address, Add, is displayed. Press the SET
key until the communication speed, InT, appears.
Interval time set value
SET
R/S
SV
PV
ALM2ALM1AT OUT2OUT1