Instruction manual

4. COMMUNICATION SETTINGS
IMCB14-E1
10
4.4 Communication Speed Setting
The communication speed of 2400bps, 4800bps, 9600bps or 19200bps is set with numbers from 0 to 3.
To change the number of the digit, press the UP or DOWN key.
Symbol Name Setting range Description
Factory set
value
Communication
speed
0 : 2400 bps
1 : 4800 bps
2 : 9600 bps
Select the communication
speed
2
bPS 3 : 19200 bps
Set the same communication speed for both the slave and the master.
When the communication parameter is changed, turn the power on and off again to refresh and
make the new value effective.
All communication speed settings must be stored by pressing the SET key. If changes are
made and the SET key is not pressed within one minute, the display will automatically return
to the PV/SV display mode and the communication speed will return to the value prior to set
change.



Setting procedure
Example: Setting the communication speed to 1: 4800 bps
1. Go to the communication setting mode so that slave address, Add, is displayed. Then, press the
SET key once, so the communication speed symbol, bPS, appears.
Communication speed
SET
R/S
SV
PV
ALM2ALM1AT OUT2OUT1