4. COMMUNICATION SETTINGS
IMCB14-E1
8
4.3 Slave Address Setting
The slave address must be set before Modbus communication can begin. The slave address number
is set with numbers from 1 to 99. The factory set value is 0 and two-way communication is not
possible when the address is 0.
Symbol Name Setting range Description
Factory set
value
Slave address 1 to 99* Set the controller slave
address.
0
Add
* Two-way communication is not possible when the address is 0.
When the communication parameter is changed, turn the power on and off again to refresh and
make the new value effective.
All slave address settings must be stored by pressing the SET key. If changes are made and
the SET key is not pressed within one minute, the display will automatically return to the
PV/SV display mode and the slave address will return to the value prior to set change.
Setting procedure
Example: Setting the slave address to 15
1. Go to the communication setting mode so that slave address, Add, is displayed.
Slave address
SET
R/S
SV
PV
ALM2ALM1AT OUT2OUT1