Instruction manual
IMCB04-E2
1
1. TRANSFER TO MODE
Initialization is to set parameters relating to instrument specifications (input type, input range, alarm
type, etc.) and those relating to instrument characteristics (setting limiter, alarm differential gap, etc.).
1.1 Transfer to initialization mode
• Turn on the power to this instrument. Thus, the input type, input range and PV/SV display mode
change in this order.
‚ Press the SET key for 2 sec with the instrument set to PV/SV display mode to change the
instrument to parameter setting mode.
*For details on parameter setting mode, see the instruction manual for
CB100 [IMCB01-E
¨
]
or
CB400/CB500/CB700/CB900 [IMCB02-E
¨
]
.
ƒ Press the SET key to change to the set data lock function display screen.
„ Press the <R/S key to light brightly the thousands digit on the set value (SV) display unit.
SET
R/S
OUT1 OUT2
AT ALM1
SV
PV
ALM2
Set data lock function display
… Press the UP key to change "0" to "1" in the thousands digit.
SET
R/S
OUT1 OUT2
AT
ALM1
SV
PV
ALM2
Set data lock function display
Set value
0 : Initialization mode locked
1 : Initialization mode unlocked
Bright lighting :
Dim lighting :
As the units digit light brightly first,
press the <R/S key to light brightly
the thousands digit.
Dim lighting :
Bright lighting :