Instruction manual

3. COMMUNICATION INITIALIZE IDENTIFIER
IMCB04-E2
29
ID
: Identifier
(RO : Read only R/W :
Read/write)
Name ID Data range Factory
set value
R/W
Factor to calculate proportional band
setting
[STPK]
PU 0 to 200 67 R/W
Factor to calculate derivative time
setting
[STIK]
IU 0 to 200 16 R/W
Holding peak ambient temperature
[TCJ]
HP
-10 to +100°C
0RO
Operating time display unit
(Upper digits)
[WTH]
UT 0 to 10 0 RO
Operating time display unit
(Lower digits)
[WTL]
UU 0 to 9999 0 RO
*1...
Input type Set value
K0
J1
L2
E3
N4
T5
U6
R7
S8
B9
W5Re/W26Re 10
Thermocouple
input (TC)
PL II 11
Pt100 (JIS/IEC)
12
RTD input
(RTD)
JPt100 (JIS)
13
0 to 5 V DC 14Voltage input
1 to 5 V DC 15
0 to 20 mA DC 14Current input
4 to 20 mA DC 15