Instruction manual
3. COMMUNICATION INITIALIZE IDENTIFIER
IMCB04-E2
28
ID
: Identifier
(RO : Read only R/W :
Read/write)
Name ID Data range Factory
set value
R/W
Control action type selection
[SL6]
CA 0 to 15 See *3 To vary
depending on
the specificatio
n
R/W
Energized/de-energized alarm
selection, special specification
selection 1 [SL7]
Z1 0 to 15 See *4 0 R/W
Special specification selection 2
[SL8]
Z2 0 : Z-185 specification not
provided
2 : Z-185 specification provided
0R/W
Special specification selection 3
[SL9]
Z3 0 : Z-168 specification provided
1 : Z-168 specification not
provided
0R/W
Option selection [SL10] DH 0 to 13 See *5 0 R/W
SV alarm type selection [SL11] XC 0 to 15 See *6 0 R/W
Setting limiter (high limt)
[SLH]
XV See "Input range table"
(P.19, 20, 21)
To vary
depending on
the specificatio
n
R/W
Setting limiter (low limit) [SLL] XW
Setting the position of decimal point
[PGdP]
XU 0 : No digit below decimal point
1 : 1 digit below decimal point
2 : 2 digits below decimal point
3 : 3 digits below decimal point
1R/W
Differential gap setting of ON/OFF
action
[oH]
MH
l
For TC/RTD inputs : 0 (0.0)
to100 (100.0) °C [°F]
l
For voltage/current inputs :
0.0 to 10.0% of span
See *7 R/W
Differential gap setting of first alarm
(ALM1)
[AH1]
HA
l
For TC/RTD inputs : 0 (0.0)
to100 (100.0) °C [°F]
l
For voltage/current inputs :
For voltage/current inputs :
See *7 R/W
Differential gap setting of second
alarm (ALM2)
[AH2]
HB 0.0 to 10.0% of span
CT ratio setting
[CTr]
XR 0 to 9999 See *8 R/W
Digital filter setting [dF] F1 0 to 100 sec 0 R/W
Time factor assumed to be safe setting
[STTM]
GH 0 to 200 100 R/W
Continued on the next page.