2. PROCEDURE FOR SETTING
IMCB04-E2
25
(10) STPK (Factor to calculate proportional band setting)
*Displayed when the self-tuning is provided.
This is the factor to adjust the proportional band to be calculated by the self-tuning function. The larger
the set value, the larger the proportional band thus calculated.
As this factor is so adjusted that the self-tuning result optimum to most controlled-objects
is obtained, do not change it.
Setting range : 0 to 200
Factory set value : 67
(11) STIK (Factor to calculate derivative time setting)
*Displayed when the self-tuning is provided.
This is the factor to adjust the integral and derivative times to be calculated by the self-tuning function.
The larger the set value, the larger the integral and derivative times thus calculated.
As this factor is so adjusted that the self-tuning result optimum to most controlled-objects
is obtained, do not change it.
Setting range : 0 to 200
Factory set value : 16
CAUTION