(7) CTr (CT ratio setting)
Set the number of times that a wire is wound on to the hole of a CT.
Not displayed when there is no heater break alarm (HBA).
Setting range : 0 to 9999
Factory set value : CTL-6-P-N : 800
CTL-12-S56-10L-N : 1000
(8) dF (Digital filter setting)
Setting range : 0 to 100 sec (If "0" is set, the PV digital filter is turned off.)
Factory set value : 1
(9) STTM (Time factor assumed to be safe setting)
*Displayed when the self-tuning is provided.
This is the factor to adjust the reference time of establishing the stabilized state of a measured value. The
larger the set value, the longer the time until the measured value is stabilized.
As this factor is so adjusted that the self-tuning result optimum to most controlled-objects
is obtained, do not change it.
Setting range : 0 to 200
Factory set value : 100