Instruction manual

2. PROCEDURE FOR SETTING
IMCB04-E2
18
(2) SLL (Setting limiter [low limit] )
l
Set the limiter by referring to "Input range table." (P.19)
l
Limiter setting becomes SLH SLL.
n
Setting method
Press the <R/S key to move the digit, then enter the low limit value of input range by
pressing the UP or DOWN key.
The set value (SV) display unit shows the numeric value.
Factory set value varies depending on the instrument specification.
Input type Setting range
K
0 to 1372 °C (0 to 2502 °F)
J
0 to 1200 °C (0 to 2192 °F)
R
0 to 1769 °C (0 to 3216 °F)
S
0 to 1769 °C (0 to 3216 °F)
B
0 to 1820 °C (0 to 3308 °F)
E
0 to 1000 °C (0 to 1832 °F)
N
0 to 1300 °C (0 to 2372 °F)
T
-199.9 to +400.0 °C (-199.9 to +752.0 °F)
W5Re/W26Re
0 to 2320 °C (0 to 4208 °F)
PL II
0 to 1390 °C (0 to 2534 °F)
U
-199.9 to +600.0 °C (-199.9 to +999.9 °F)
Thermocoupl
e
input (TC)
L
0 to 900 °C (0 to 1652 °F)
Pt100 (JIS/IEC)*1 -199.9 to +649.0 °C (-199.9 to +999.9 °F)
RTD input
JPt100 (JIS) -199.9 to +649.0 °C (-199.9 to +999.9 °F)
0 to 5 V DCVoltage
input
1 to 5 V DC
-1999 to +9999
(programmable scale)
0 to 20 mA DC*2Current
input
4 to 20 mA DC*2
-1999 to +9999
(programmable scale)
*1 : IEC (International Electrotechnical Commission) is equivalent to JIS, DIN and
ANSI.
*2 : For the current input specification, a resistor of 250 must be connected between
the input terminals.