Instruction manual

2. PROCEDURE FOR SETTING
IMCB04-E2
16
(11) SL11 (SV alarm type selection)
l
For the instrument without "First alarm (ALM1)" or "Second alarm (ALM2)," always set it
to "0 : first alarm, SV alarm not provided," or "0 : second alarm, SV alarm not provided."
l
The following conditions must be satisfied in order to effectuate "SV alarm."
Ÿ
When setting the instrument to "First alarm, SV alarm provided"
"First alarm (ALM1) type or first alarm (ALM1) with hold action selection (SL4)"
should be set to "0000."
The content of the "SL4" setting has priority over that of the "SL11" setting.
Ÿ
When setting the instrument to "Second alarm, SV alarm provided"
"Second alarm (ALM2) type or second alarm (ALM2) with hold action selection (SL5)"
should be set to "0000."
The content of the "SL5" setting has priority over that of the "SL11" setting.
Factory set value : "0000"
Set value
Description
0 First alarm, SV alarm not provided
1 First alarm, SV alarm provided
Selection of first alarm,
SV alarm
0 First alarm, SV high alarm
1 First alarm, SV low alarm
Selection of first alarm,
SV alarm type
0 Second alarm, SV alarm not provided
1 Second alarm, SV alarm provided
Selection of second alarm,
SV alarm
0 Second alarm, SV high alarm
1 Second alarm, SV low alarm
Selection of second alarm,
SV alarm type