Instruction manual

2. PROCEDURE FOR SETTING
IMCB04-E2
15
(9) SL9 (Special specification selection 3)
l
Any item set in the "Z-168" specification has priority over that set in SL3 (heater break
alarm selection).
l
Any digits other than the units digit are not used. As malfunction may result, do not
change any of other digits.
Factory set value : "0000"
Set value
Description
0 Z-168 specification not provided *1
1 Z-168 specification provided *2
Special specification selection
0 0 0 Fixed
*1 : It becomes the item set in SL3 (heater break alarm selection).
*2 : Heater break alarm for three-phase heater.
(10) SL10 (Option selection)
l
For the A or W control action type, there is no self-tuning function (0 : self-tuning not
provided).
l
The tens digits is not used. As malfunction may result, do not change this digit.
Factory set value : "1001"
Set value
Description
0 RUN/STOP not provided
1 RUN/STOP provided
Selection of RUN/STOP
function
0 Fixed
0 Communication function not provided
1 Communication function provided
Selection of communication
function
0 Self-tuning not provided
1 Self-tuning provided
Selection of self-tuning function
CAUTIONS
CAUTIONS