Instruction manual

2. PROCEDURE FOR SETTING
IMCB04-E2
14
(7) SL7 (Energized/de-energized alarm selection, special specification selection 1)
Instrument without the first alarm (ALM1) and second alarm (ALM2) is set to "0000."
Ÿ
Instrument without the second alarm (ALM1). [SL4 setting details : For "0000"]
Ÿ
Instrument without the second alarm (ALM2). [SL5 setting details : For "0000"]
Factory set value : "0000"
Set value
Description
0 Energized alarm
1 De-energized alarm
Energized alarm/De-energized
alarm selection (First alarm
side)
0 Energized alarm
1 De-energized alarm
Energized alarm/De-energized
alarm selection
(Second alarm side)
0 Z-124 specification not provided *1
1 Z-124 specification provided *2
Special specification selection
(First alarm side)
0 Z-124 specification not provided *1
1 Z-124 specification provided *2
Special specification selection
(Second alarm side)
*1 : The alarm output is forcibly turned ON when the burnout function is activated.
*2 : No alarm action is taken by the burnout function. (Same as the normal alarm action.)
(8) SL8 (Special specification selection 2)
Any digits other than the tens digit are not used. As malfunction may result, do not change
any of other digits.
Factory set value : "0000"
Set value
Description
0 Z-185 specification not provided *1
1 Z-185 specification provided *2
Special specification selection
0 0 0 Fixed
*1 : Normal control in the direct or reverse action is performed even if the burnout function is
activated
or not.
*2 : The control output is forcibly turned ON when the burnout function is activated.
CAUTION
CAUTION