Instruction manual

2. PROCEDURE FOR SETTING
IMCB04-E2
13
(6) SL6 (Control action type selection)
l
Conduct setting so as to meet the instrument specification. An incorrect setting may
cause a malfunction.
l
When control action is of the type D or F, "Control action type selection (Cool-side)"
setting is ignored.
Factory set value varies depending on the instrument specification.
Set value
Description
0 Direct action (D type)
1 Reverse action (F, A and W type)
Direct/reverse action selection
0 PID action with autotuning *1
1 Heat/Cool PID action with autotuning *2
Control action type selection
0 Heat-side time proportioning output
(M, V, G and T output) *3
1 Heat-side continuous output
(Current 4 to 20 mA DC)
Control output type selection
(Heat-side)
0 Cool-side PID action with autotuning
(M, V and T output) *3
1 Cool-side continuous output
(Current output 4 to 20 mA DC)
Control output type selection
(Cool-side)
*1 žžž
D type
: PID action with autotuning (Direct action)
F type
: PID action with autotuning (Reverse action)
*2 žžž
A type
: Heat/cool PID action with autotuning (Air cooling)
W type
: Heat/cool PID action with autotuning (Water cooling)
*3 žžž
M output
: Relay contact output
G output
: Trigger (for triac driving) output
V output
: Voltage pulse output
T output
: Triac output
CAUTIONS