Instruction manual

2. PROCEDURE FOR SETTING
IMCB04-E2
12
(5) SL5 (Second alarm [ALM2] type or second alarm [ALM2] with hold action
selection)
The following instrument is set to "0000."
Ÿ
Instrument without the second alarm (ALM2).
Ÿ
Instrument with the heater break alarm (HBA).
Ÿ
Instrument which outputs control loop break alarm (LBA) from the second alarm side.
(SL3 setting details : For "1010")
Factory set value varies depending on the instrument specification.
Set value
Description
0 0 0 Second alarm (ALM2) not provided
0 0 1 Deviation high alarm
0 1 0 Deviation high/low alarm
0 1 1 Process high alarm
1 0 1 Deviation low alarm
110 Band alarm
1 1 1 Process low alarm
Second alarm (ALM2) type
selection
0 Without alarm hold action
1 With alarm hold action
Second alarm (ALM2) with hold
action selection
CAUTION