Instruction manual

4
IMCB04-E2
2. PROCEDURE FOR SETTING
If the instrument is changed to initialization mode, the symbol (Cod) for selecting the initialize code is
displayed first. (Initializing items are classified into 3 initialize code groups in
initialization mode.)
Enter the initialize code corresponding to the parameter to be changed, and then select the parameter
to be changed by pressing the SET key. The measured value (PV) display unit shows the characters
corresponding to the parameter, and the set value (SV) display unit shows the value corresponding to
that parameter. Display flowcharts in initialization mode are shown in the following.
2.1 Display flowcharts in initialization mode
Set " " to 0.
Input type selection
Engineering unit and
cooling type selection
Heater break alarm,
control loop break alarm,
special specification, or
control loop break alarm
output selection
First alarm (ALM1) type
or first alarm (ALM1)
with hold action
Second alarm (ALM2)
type or second alarm
(ALM2) with hold action
Control action type
selection
Energized/de-energized
alarm selection,
special specification
selection 1
Special specification 2
Special specification 3
Option selection
SV alarm type selection
Setting limiter
[high limit]
Setting the position
of decimal point
Differential gap
setting of first alarm
(ALM1)
Differential gap
setting of second
alarm (ALM2)
CT ratio setting
Differential gap
setting of
ON/OFF action
Explaining the arrow mark :
Press the SET key.
Set " " to 1. Set " " to 2.
Initialize code selection
Time factor assumed
to be safe setting
Digital filter
setting
Factor to calculate
proportional band
setting
Factor to calculate
derivative time setting
Holding peak ambient
temperature
Operating time display
unit (Upper digits)
Operating time display
unit (Lower digits)
*Parameters in this initialize code are only
displayed.
Initialize code selection
(SL1)
(SL2)
(SL3)
(SL4)
(SL5)
(SL6)
(SL8)
(SL7)
(SL9)
(SL10)
(SL11)
(SLH)
(SLL)
(PGdP)
(oH)
(AH1)
(AH2)
(CTr)
(dF)
(STTM)
(STPK)
(STIK)
(TCJ)
(W TH)
(W TL)
Setting limiter
[low limit]
CAUTION
There are parameters which are not displayed depending on the specification.
Parameter setting mode Communication setting mode
Keep pressing the SET and <R/S keys simultaneously
for 2 sec with the set data unlocked.
Press the SET and <R/S keys
simultaneously for 2 sec.
Press the SET key
for 2 sec.
PV/SV display mode
Press the SET and <R/S keys simultaneously