Technical data
Page 17/ 24 34-81 10/2013
6.6 OUTPUT 3 ALTERNATE SET POINT
Kind of action: Heating
Reference probe: TP1 or TP2
Related Parameters: St3, Hy3, LS3, US3, AC3, St5, Hy5, 3on, o3P, SSE, AC5, ACA
NOTES
1. When SSE is enabled and Output 1 is in a de-energized state (off) Output 3 will function according to St3. When
Output 1 is in an energized state Output 3 will function according to St5.
2. ACA delays the change from St3 to St5.
3. o3P selects temperature probe to be referenced by Output 3.
4. Hy1, Hy3 and Hy5 are active but not shown in this illustration.
Set-Point
Shift
Set 3
Set 1
Set 5
On
Out 3
Off
On
Out 1
Off
Time
Set 3
Set 5
Set 3
Alternate Set Point Control
Set 5
ACA Time
Dela
y