Technical data

Page 15/ 24 34-81 10/2013
6.3 OUTPUT 2 2ND STAGE (oS2=Std 2on=rEG)
Kind of action: Heating
Reference probe: TP1
Terminals: SPADE 6 & 7
Related Parameters: S2c, St2, Hy2, LS2, US2, AC2, oS2, 2on
time
time
Out2
Probe1
Set2
Set2+ Hy2
NOTES
1. Output 2 will function as an output temperature control when oS2=Std, otherwise output 2 is an alarm output
contact.
2. S2c determines if St2 is relative to St1 or independent. (S2c=dep or ind).
3. Hy2 functionality same as Hy1. See OUTPUT 1 CALL FOR HEAT.
6.4 OUTPUT 2 AS ALARM RELAY (oS2=AL, 2ON=REG)
1. Output 2 will function as an alarm contact when oS2=AL.
2. When an alarm condition occurs, Output 2 will be energized (relay closes) as an indication of an alarm condition.
3. Terminals: SPADE 6 & 7.