Technical data
Page 12/ 24 34-81 10/2013
Label
Firm
Version Description
Range
X÷YFromXtoY
Rev 0.3
Level
Rev 0.5
Level
Hex
Modbus
Address
Base 0
Modbus
Command
Address
40000+
S5
0.3 & 0.5
EnergysavingstoponThursday 0÷23h50min.‐nu
Pr2 Pr2
0x348 841
Sb5
0.3 & 0.5
SetbacktemperatureonThursday‐40÷40°F
Pr2 Pr2
0x349 842
E6
0.3 & 0.5
EnergysavingstartonFriday 0÷23h50min.‐nu
Pr2 Pr2
0x34A 843
S6
0.3 & 0.5
EnergysavingstoponFriday 0÷23h50min.‐nu
Pr2 Pr2
0x34B 844
Sb6
0.3 & 0.5
SetbacktemperatureonFriday‐40÷40°F
Pr2 Pr2
0x34C 845
E7
0.3 & 0.5
EnergysavingstartonSaturday 0÷23h50min.‐nu
Pr2 Pr2
0x34D 846
S7
0.3 & 0.5
EnergysavingstoponSaturday 0÷23h50min.‐nu
Pr2 Pr2
0x34E 847
Sb7
0.3 & 0.5
SetbacktemperatureonSaturday‐40÷40°F
Pr2 Pr2
0x34F 848
WORKING HOURS
ou1
0.3 & 0.5
workinghoursactualofrelay1 0÷9999h
Pr1 Pr2
0x350 849
ou2
0.3 & 0.5
workinghoursactualofrelay2 0÷9999h
Pr1 Pr2
0x351 850
ou3
0.3 & 0.5
workinghoursactualofrelay3 0÷9999h
Pr2 Pr2
0x352 851
oP1
0.3 & 0.5
workinghourslimitofrelay1
0÷9999h;with0the
functionisdisabled Pr2 Pr2
0x353 852
oP2
0.3 & 0.5
workinghourslimitofrelay2
0÷9999h;with0the
functionisdisabled Pr2 Pr2
0x354 853
oP3
0.3 & 0.5
workinghourslimitofrelay3
0÷9999h;with0the
functionisdisabled Pr2 Pr2
0x355 854
OUTPUTS SETTING
1on
0.3 & 0.5
Theoutput1isalwaysonordependingontemperature
rEG=1,1;YES=0,1;
no=0,0 Pr2 Pr2
0x356 855
2on
0.3 & 0.5
Theoutput2isalwaysonordependingontemperature
rEG=1,1;YES=0,1;
no=0,0 Pr2 Pr2
0x357 856
3on
0.3 & 0.5
Theoutput3isalwaysonordependingontemperature
rEG=1,1;YES=0,1;
no=0,0 Pr2 Pr2
0x358 857
OTHER
Adr
0.3 & 0.5
Serialaddress 0÷247
Pr2 Pr2
0x359 858
Ptb
0.3 & 0.5
Parametermapcodealways=1 readableonly
Pr2 Pr2
0x35A 859
rEL
0.3 & 0.5
Softwarerelease5=0.5,3=0.3 readableonly
Pr2 Pr2
0x35B 860
i1S
0.5
AnalogoutputwhenDigitalInput1isactivated 4‐20mA
Pr2
0x35C 861
i1t
0.5
Analogoutputati1SextratimeifDigitalInput1isnot
activated
0÷30sec.
Pr2
0x35D 862
i1d
0.5
DigitalInput1AlarmDelay 0÷255min.
Pr2
0x35E 863
i1F
0.5
IfYes,DigitalInput1willfunctionasAlarm.Operating
onlywhentryingtocallforoutput1andInput1is
active,subjecttoi1dtimer
No;Yes
Pr2
0x35F 864
i2F
0.5
DigitalInput2willfunctiononlywhenOutput1is
energized
No;Yes
Pr2
0x360 865
i3F
0.5
DigitalInput3willfunctiononlywhenOutput1is
energized,WhenEdiisselected,Output1willopen
whendigitalinput3isactivated
No;Yes;Edi
Pr2
0x361 866
oS2
0.5
Output2function:eithertemprelayoralarmrelay Std;AL
Pr2
0x362 867
0.3 & 0.5
Probe1temperature DegreesF/C
Pr2
0x100 257
0.3
Probe1Information/StatusNormal=512or0x0200,
Fault=515or0x0203.Faultwill,dropcallforheat,buz,
FlashYellowP1,lightyellowvalve/M
bit(0,1on)probe
failure
Pr2
0x101 258
0.3 & 0.5
Probe2temperature DegreesF/C
Pr2
0x102 259
0.3
Probe2Information/StatusNormal=512or0x0200,
Fault=515or0x0203.Faultwillbuz,FlashRedP2
bit (0,1on)probe
failurePr2
0x103 260
0.3 & 0.5
Probe3temperature DegreesF/C
Pr2
0x104 261