Specifications
Riverside Hydronics
®
, LLC WWW.RIVERSIDEHYDRONICS.COM 34-151 06/2014
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918 Page | 7
The Remote Equipment feature is provided for the activation of equipment such as circulation pumps,
air louvers and active ventilation systems. When there is a call for heat the OnTrac will energize the
remote equipment contacts and wait for a set time for any Remote Proving circuits to be energized.
There are two relay outputs provided. See Programming
Manual 34-152 for details.
• There are two Remote Equipment outputs
available. Both relays are rated for 110VAC with a
maximum switching current of 10A.
• Connect the load for control circuit 1 to P1 and P2.
This is a N.O. contact and will be open on power
failure and closed on call for remote equipment.
• Connect the load for control circuit 2 to P3 and P4.
This is a N.C. contact and will be closed on power
failure and open on call for remote equipment.
The Remote Alarm contacts are provided as a remote indication of a system alarm. This indication is not
specific in nature but intended to alert the user of a problem. Details of the alarm condition can be
found by viewing the Boiler Status screen on the OnTrac
or at the individual boiler.
• The relay contacts for this feature are rated for
110VAC with a maximum switching current of
10A.
• Connect the alarm load to A1 and A2.
W
IRING THE REMOTE EQUIPMENT RELAY
S
W
IRING THE REMOTE ALARM RELAY
S