Specifications

Riverside Hydronics
®
, LLC WWW.RIVERSIDEHYDRONICS.COM 34-151 06/2014
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918 Page | 7
The Remote Equipment feature is provided for the activation of equipment such as circulation pumps,
air louvers and active ventilation systems. When there is a call for heat the OnTrac will energize the
remote equipment contacts and wait for a set time for any Remote Proving circuits to be energized.
There are two relay outputs provided. See Programming
Manual 34-152 for details.
There are two Remote Equipment outputs
available. Both relays are rated for 110VAC with a
maximum switching current of 10A.
Connect the load for control circuit 1 to P1 and P2.
This is a N.O. contact and will be open on power
failure and closed on call for remote equipment.
Connect the load for control circuit 2 to P3 and P4.
This is a N.C. contact and will be closed on power
failure and open on call for remote equipment.
The Remote Alarm contacts are provided as a remote indication of a system alarm. This indication is not
specific in nature but intended to alert the user of a problem. Details of the alarm condition can be
found by viewing the Boiler Status screen on the OnTrac
or at the individual boiler.
The relay contacts for this feature are rated for
110VAC with a maximum switching current of
10A.
Connect the alarm load to A1 and A2.
W
IRING THE REMOTE EQUIPMENT RELAY
S
W
IRING THE REMOTE ALARM RELAY
S