Specifications

Riverside Hydronics
®
, LLC – 34-160 10/11
990 Haltom Road - Fort Worth, Texas 76117 - Tel 1-800-990-5918 Page | 9
TheTIER1menushouldbethefirstmenuused.ThismenuwillapplytosingleTierboilersystemswhere
allofthe boilers areofthesametype,suchasallcondensingorallnoncondensing.Itwillalsobeused
tosetupthefirstTierofthe
twoTier(FrontEndLoadedSystem).
ThefirstentrybuttonistitledFIRSTTIERBOILERS.Pressthisbuttonandyouwillbepromptedto
enter the number of first Tier boilers in your system. If all your boilers are of one type, this
parameterwillbethetotalnu mber
ofboilersinyoursystem.
The CYCLE PERIOD parameter will
define the interval at which
OnTrac®
will change assignment of the lead
boiler position. This value can be from
(1to7days).Thecycleper iodwillbegin
to the count down at the time of
commissioning.
CURRENT LEAD BOILER shows which
boiler is currently assigned the lead
boilerposition.
SYSTEM DIFFERENTIAL allows the user
to define the temperature range over which the
OnTrac®
will seek to maintain temperature
control.Range(5to15°F).GotoLEAD/ LAG2toadjustthisparameter.
CYCLEOCCURSdefinesthetimeofdaythe
OnTrac®
willchangetheleadboiler assignment.Go
toLEAD/LAG2toadjustthisparameter.
CHANGE LEAD BOILER allows the user to immediately change assignment if the lead boiler
position.
SYSTEM SETPOINT allows the user to choose the temperature at which
OnTrac®
will seek to
maintaintheboilersystem.
ADJUSTED SETPOINT displays the set point after a reset function such as Outdoor Reset,
ScheduledSetbackorRemoteSetpointadjustmenthavebeenmade.
SYSTEMTEMPERATUREdisplaysthecurrentsystemtemperature.
TURNONSYSTEMSENSORwillenableordisablethesensorprobe.
THE TIER 1 MENU