Specifications

Riverside Hydronics
®
, LLC – 34-160 10/11
990 Haltom Road - Fort Worth, Texas 76117 - Tel 1-800-990-5918 Page | 7
This section will provide the necessary instructions for quickly commissioning a one or two Tier
boilersystem.
1. Once the boiler addresses have
been assigned, add up the total
numberofboilersinyour firstTier
and enter that number in the
FIRST TIER BOILERS box. If your
boiler system
only contains one
type of boiler, condensing only or
non‐condensing,skipstep2.
2. Enter the total number of boilers
inyoursecondTierintheSECOND
TIER BOILERS box. In a two Tier
boilersystem,Tier2wouldcontain
theNon‐condensingboilers.IfTier2isintended
forindependentoperation,seepage20for
setupinstructions.
3. SettheSYSTEMSETPOINT.
4. TheSYSTEM SENSOR is au tomatically turned on and assigned to boiler 1 probe 3. Confirm
thattheSYSTEMTEMPERATUREis registeringasensedtemperature.
5. Yoursystemshouldnowbeoperational.
QUICK SETUP OF A 1 OR 2 TIER SYSTE
M