When nonRiverside Hydronics boilers are operated as the Tier2 boilers, the optional TempTrac
BoilerControlmodule can be applied as a fully functional operating control or used to enableand
disableonly.Thisscreenallowsthatfunctionalselectiontobechosenforeachboiler.
The enable/disable (O N/OFF ONLY)
button, when pushed, will program the TempTrac
Control Module to turn the boiler on or off only. The modulation, staging and primary
temperatureregulationfunctionwillbecontrolledbytheexistingboilercontrols.Warning:
Donotdisabletheexistingboilercontrolsorbypasstheexistingtemperaturelimits.When
the (ON/OFF
ONLY) function is used the TempTrac temperature sensor can be used for
displaying the boiler temperature only or left to display the room temperature. Do not
disconnectsensor.
The(FULLCONTROL)buttonwillprogram theTempTracControl Moduletoprovidethefull
temperatureregulationcontrolandmonitoringfunction.Ifyour
Tier2boilersareRiverside
Hydronicsboilers,thisisthedefaultsetting.Ifa nonRiverside Hydronicsboilerisusedand
full control is desired, the control module must be wired according to the OnTrac
Installation and Wiring Guide (34151). The temperature sensor must be installed in a
location
thatallowsthecontrol moduletomonitortheboilerwatertemperature.Warning:
Donotbypasstheexistingboilerlimits.