TheTIER2INDEPENDENTOPERATION,whenactivated, separatesthefunction ofTier1 andTier2.
Thiseffectivelyallowstheusertocontr oltwoseparatehydronicsystemswithoneOnTrac®.Tier2is
assigneditsownloopsensor,whichcanbeconnectedtoanyboile r intheTier2system.
Assign the TIER 2 SENSOR ADDRESS.
The default address is 13 but can be
any address in the Tier 2 boiler
system(13‐20).
PushthebuttonTURNONT2SYSTEM
SENSORtoac tivatethesensor.
TurnontheINDEPENDENTfunction.
Although the TIER 2 INDEPENDENT
OPERATION
is controlled indep endently of
Tier1,theSystemSetpointmustbethesame
asTier1.
OthercontrolfunctionsthatactontheSystemSetpointsuchasOutdoorReset,ScheduledSetback
andRemoteSetpointalsoactonTier1andTier2 thesame.
Lead Lag functions such as CYCLE PERIOD,
CYCLE OCCURS and SYSTEM DIFFERENTIAL setting are
uniquetoeachTierandcanbeadjustedseparately.
BoilersineitherTier1orTier2canbelocated upto1000metersfromtheOnTrac®control.
TIER 2 INDEPENDENT OPERATIO