The OPTIONS SCREEN con tains links to other screens and parameters which will be rarely used. A
trainedtechnicianshouldbeconsultedbeforeanychangesaremade.
SENSORSELECTIONallowstheusertochangethedefaultsensorlocationsasrequired.
TIER 1 LEAD/LAG and TIER 2 LEAD/LAG is a
time
delayparameteradjustablefrom5to30
minutes. This delay occurs between the drop
in loop temperature and the call for
additionalboilerstobeenabled.
FIRING RATE LAG TRIGGER is an alternate
Lead/Lag me thod which when turned on will
enableLag boilers based on the firing rate of
the preceding boiler. The Firing Rate
Thresholdcanbesetatbetween50and100percent.Forexample,ifthisfunctionissetat
70, OnTrac® will enable the Lag boiler when the firing rate of the Lead boiler or the
precedingboilerreaches70percent.
REMOTE EQUIPMENT s creen allows
the user to temporarily override and turn on the
RemoteEq uipmentoutputsandProvingInputs.ThisScreenalsoincludestheWATERVALVE
CONTROLSWITCH.
The Temptrac screen is an interface for communicating directly with an individual
TempTrac. Throughthis screen a train ed technician can readorwrite to specific
registers.
Thisscreenispasswordprotected.
The FACTORY screen contains parameters
which should only be accessed by factory
personnel.
MANUAL OVERRIDE shown to the right,
allowstheusertoforceon,forceofforrun
individual boilers in automatic. This
function should be used at the time of
commissioning
orservices.Caution:Boilers
should not be left in the FORCE ON mode
unattended.
OPTIONSCREEN2isdescribedinthenextsection.
Theotherscreenaccess buttonsshownon the OPTIONS menu aredescribedelsewherein
thismanual.