Specifications

Riverside Hydronics
®
, LLC – 34-160 10/11
990 Haltom Road - Fort Worth, Texas 76117 - Tel 1-800-990-5918 Page | 15
TheBOILERSTATUSDISPLAYscreenis designed to allowtheuser to getmoredetailedinformation
aboutaparticularboiler.
TheBOILERADDRESSisadataentrybutton.Pressthisbuttonandenterthedesiredboiler.Once
theboileraddresshasbeenentereditmaytakeupto30seconds
tocompilethescreendata.
LEAD BOILER displays the current lead
boileraddress.
BOILER STATE is a color coded display
indicating the On/Off status of the
boiler.
ALARM is a color coded display
indicating whether or not an alarm
conditioncurrentlyexistforthisboiler.
HOURS
OFOPERATIONdisplaysinhours
the total run time for this boiler. Push
the HOURS UPDATE button to see the
currenthoursofoperation.
RETURN is both a bar graph and a numerical display of the return (inlet) temperature of the
boiler.
SUPPLY is both a bar graph and
a numerical display of the suppl y (outlet) temperature of the
boiler.
FIRINGRATEisboth abargraphanda numericaldisplayofthepercentofthe modulationscale
orrangeoffiringrateoftheboiler.
SETPOINTisthecurrentsetpointforthisboiler.
ADJUSTED
SETPOINT displays the set point after a reset function such as Outdoor Reset,
ScheduledSetbackorRemoteSetpointadjustmenthavebeenmade.Thisisthesameparameter
asislocatedontheTier1menu.
BOILERSETPOINTisthecurrentsetpointforthisboiler.
Intheeventthatcommunication
withboilersislost,thelastdatastoredwillremaindisplayed.
BOILER STATUS DISPLA
Y