Specifications

Riverside Hydronics
®
, LLC – 34-160 10/11
990 Haltom Road - Fort Worth, Texas 76117 - Tel 1-800-990-5918 Page | 11
The TIER 1 SYSTEM STATUS screen is provided to monitor the most commonly need system
informationformultipleboiler.Thefirstscreendisplaythisinformationforuptoeightboileranda
supplementalscreenTIER 19‐12displaysthesameinformationforboilers9to12.
SYSTEM
TEMPdisplaysthecurrentsystemtemperature.
OUTDOOR TEMP displays the
currentsystemtemperature.
ADJUSTED SETPOINT displays the
set point after a reset function
such as Outdoor Reset, Scheduled
Setback or Remot e Setpoint
adjustment have been made. This
is the same parameter as is
locatedontheTier1menu.
SETPOINT is the current
set point
foreachboilerinthesystem.
INLETthisisthecurrentmeasuredreturnwatertemperatureofeachboiler inthesystem.
OUTLETthisisthecurrentmeasuredsupplywatertemperatureofeachboilerinthesystem.
The OUTLET temperature displays can be turned off when not used
as shown here by
touchingthedisplay.
Thenumericaldisplayboxeslocatedatthebottomofthescreenindicatedthetimeelapsed
asthe controlcountsuptoenabletherespectiveboiler (top)or downtodisable (bottom).
ThetotaltimeisenteredonOPTIONSCREEN1.
Thereis
aTIER2SYSTEMSTATUSscreenwhichprovidesthesameinformationfortheTier2boilers
withaddressesfrom13to20.