The TIER 2 menu will only be used when a “Front‐end Loaded” boiler system is applied. The 2 Tier
systemisdesignedtousehighefficiencycondensingboilersastheprimaryheatsourceforthemajority
oftheheatingseasonbutuselessefficientnon‐condensingboilersforaddition al
heatwhenthesystem
loadisexceptionallyhigh.The
OnTrac®
doesthisbyconcentratingthedistributionofloadtotheTier1
boilerswhile cyclingthelead/lagpriority.WhenthesystemloadexceedsthecapacityofTier1
OnTrac®
willincrementallybringontheTier2boilersalsocyclin gthelead/lagpriorityofTier2.
ThefirstentrybuttonistitledSECONDTIERBOILERS.Pressthisbuttonandyouwillbeprompted
toenterthenumberofTier2boilersinyoursystem.Thisparameterwillbethenumber
ofTier2
boilersonly.TheFIRSTTIERBOILERShowevershouldonlyreflectthenumberofTier1boilers.
The CYCLE PERIOD parameter will define the
intervalatwhich
OnTrac®
willchangeassignment
ofthelead bo iler position. This value canbefrom
(1 to 7 days). The cycle period will begin to the
countdownatthetimeofcommissioning.
CURRENTLEAD BOILERshowswhichTier2boileris
currently assigned the lead boiler position. This
doesnotaffect
theTier1boilers.
SYSTEMDIFFERENTIALallowstheusertodefinethetemperaturerangeoverwhichthe
OnTrac®
will seek to maintain temperature control. Range (5 to 15°F). Go to LEAD/LAG 2 to adjust this
parameter.
CYCLE OCCURS defines the time of day the
OnTrac®
will change the Tier 2 lead boiler
assignment.GotoLEAD/LAG2toadjustthis parameter.
CHANGE LEAD BOILER allows the user to immediately change assignment if the lead boiler
position.
SYSTEM SETPOINT allows the user to choose the temperature at which
OnTrac®
will seek to
maintaintheboilersystem.Thisis thesameparameterasislocatedontheTier1men u.
ADJUSTED SETPOINT displays the set point after a reset function such as Outdoor Reset,
ScheduledSetbackorRemoteSetpointadjustmenthavebeenmade.Thisisthesameparameter
asis
locatedontheTier1menu.
SYSTEMTEMPERATUREdisplaysthecurrentsystemtemperature.
TIER2CONTROLMETHODallowstheusertosetupthefunctionoftheTem pTracRetroKitorthe
Tier2independentoperationmode. See page20and21fordetails.
THE TIER 2 MENU