Technical data

15
12. Comfort control display screen and system analysis
Alarm no. System message Cause Remedy
A01 Open the enclosure door Door open or door limit switch not correctly
positioned
Close door, position door limit switch correctly,
check connection if necessary
A02
Internal temperature of enclosure too
high
Cooling capacity too low/unit undersize
Sequence errors in messages A03 to A17
Check cooling capacity
A03 Filter monitoring Filter mat soiled Clean or exchange
A04
Ambient temperature too high/too low Ambient temperature outside the permissible
operating range (+10°C to +60°C)
Raise or lower the ambient temperature
(e.g. heat or ventilate the room)
A05 Icing hazard Icing hazard display according to operating
mode
Increase the nominal value of
the internal enclosure temperature
A06 PSA
H
monitor
Ambient temperature too high Unit operating limits exceeded
Condenser soiled Clean
Filter mat soiled Clean or exchange
Condenser fan defective Exchange
E-valve defective Repair by refrigeration engineer
PSA
H
monitor fault Refrigeration engineer to exchange
A07 Evaporator Refrigerant fault Repair by refrigeration engineer
A08 Condensate warning Only in units with optional condensate
evaporation
Check condensate drainage; repair kinks or
blockages in the hose as necessary
A09 Condenser fan Blocked or defective Clear the blockage; exchange if necessary
A10 Condenser fan Blocked or defective Clear the blockage; exchange if necessary
A11 Compressor
Compressor overloaded
(internal winding protection)
Unit switches in again independently
Defective (check by measuring the
winding resistance)
Refrigeration engineer to exchange
A12 Condenser temperature sensor Open or short circuit Exchange
A13 Ambient temperature sensor Open or short circuit Exchange
A14 Icing temperature sensor Open or short circuit Exchange
A15
Condensate warning temperature
Open or short circuit Exchange
A16 Internal temperature sensor Open or short circuit Exchange
A17
Phase monitoring
Incorrect rotary field/phase absent Exchange two phases
A18 EPROM error
A19 LAN/Master-Slave Master and slave not linked Setting or check cable
A20 Voltage drop Fault display is not illustrated Event is saved in the log file
E0 Display signal
Connection problem (display and control board)
Reset by means of power supply (OFF/ON)
Cable faulty; plug connection loose Replacement of the boards
The fault displays A03, A06 and A07 are to be reset manually. To do this, hold down the
and
keys simultaneously for 5 seconds.
13. Comfort control programming
Level Display
screen
changeable
parameter
min.
value
max.
value
Factory
setting
Explanation
1 St
Nominal value of
the internal
enclosure
20 55 35 The nominal value of the internal enclosure temperature is set at the factory to 35°C and is
variable over a 20°C range to 55°C.
2Fi Filter mat
monitoring
10 60
(99 = off)
99 For activation of filter mat monitoring, the display is to be set to a minimum of 10 K above
the temperature difference shown in programming mode “Fi”; filter mat monitoring is
switched off at the factory. (Display 99 = off).
3 Ad Master-slave
programming
0 19 0 see 8.3 “Cooling unit programming”
4 CF
Temperature
conversion
0 1 0 The temperature display can be switched from °C (0) to °F (1). The corresponding LED
displays the current unit of temperature.
5 H1
Temperature
switching
2 10 5 The cooling unit is set in the factory for a switching cycle of 5 K. This parameter should only
be changed after agreement with the manufacturer.
6 H2 Difference for error
message 2
3 15 5 If the internal enclosure temperature exceeds the set value by more than 5 K, then error
message 2 (internal enclosure temperature too high) appears on the display terminal. The
difference of 5 K can be changed if required over the rang 3 K to 15 K.
7 A1 Relay connection 0 2 0
The fault messages (1 to 19) depicted in the display can also be evaluated using two
potential-free fault message relays. Comfort control provides the option to group fault
messages accordingly and assign them to both fault message relays. The value “1” is to be
programmed for assignment and evaluation of the relevant fault message via relay 1.
If the fault is to be evaluated via relay 2, then the value “2” is to be programmed accordingly.
If the value is set to “0”, the system message appears only in the display.
This accordingly enables the user to define the system weighting himself, by apportioning
between relays 1 and 2.
8 A2 Relay connection 0 2 0
9 A3 Relay connection 0 2 0
10 A4 Relay connection 0 2 0
11 A5 Relay connection 0 2 0
12 A6 Relay connection 0 2 1
13 A7 Relay connection 0 2 2
14 A8 Relay connection 0 2 1
15 A9 Relay connection 0 2 1
16 A10 Relay connection 0 2 1
17 A11 Relay connection 0 2 2
18
A12
Relay connection 0 2 1
19 A13 Relay connection 0 2 1
20 A14 Relay connection 0 2 1
21 A15 Relay connection 0 2 1
22 A16 Relay connection 0 2 1
23 A17 Relay connection 0 2 1
24 A18 Relay connection 0 2 0
25 A19 Relay connection 0 2 0