Operating instructions
10 Technical specifications
Rittal fan-and-filter unit assembly and operating instructions 15
EN
Unit
Model No. SK
Fan-and-filter
unit,
RAL 7035
–
3243.100 3243.110 3244.100 3244.110 3244.140 3245.500 3245.510
EMC fan-and-
filter unit,
RAL 7035
–
3243.600 – 3244.600 – – 3245.600 –
Rated operating
voltage
V
Hz
230,
1~,
50/60
115,
1~,
50/60
230,
1~,
50/60
115,
1~,
50/60
400/460,
3~,
50/60
230,
1~,
50/60
115,
1~,
50/60
Rated current
max.
A
0.37/
0.43
0.75/
0.80
0.59/
0.81
1.0/
1.4
0.22/
0.24
1.3 2.5
Power
consumption
W 71/89 70/80 109/155 110/156 96/138 170 170
Pre-fuse T A 4 6 4 6
Motor
circuit-
breaker
4 6
Dimensions
B1/H1 mm 323 x 323
B2/H2 mm 292 x 292
T1 mm 25
T2
(max. installation
depth)
mm 118.5 130.5 130.5
Air throughput,
unimpeded air
flow
m³/h 550/600 700/770 900
Air throughput
with outlet filter
including standard
filter mat
m³/h
1 x 3243.200:
465/510
1 x 3243.200:
544/587
1 x 3243.200:
680
2 x 3243.200:
508/548
2 x 3243.200:
614/662
2 x 3243.200:
820
Outlet filter
–
3243.200
EMC outlet filter
–
3243.060
Fan – Diagonal, capacitor motor
Diagonal,
rotary
current
motor
Diagonal,
EC motor
Noise pressure
level
dB (A) 59/61 65/68 67/70 72
Operating
temperature
°C –30 to +55
Storage
temperature
°C –30 to +70
Protection
category
(to EN 60 529)
–
IP 54 standard
IP 55 with additional fine filter mat or hose-proof
hood
IP 56 with hose-proof hood
IP 51 standard
IP 52 with additional
fine filter mat
IP 56 with
hose-proof hood
Tab. 5: Technical specifications
We reserve the right to make technical modifications.