Operating instructions
10 Technical specifications
14 Rittal fan-and-filter unit assembly and operating instructions
EN
Unit
Model No. SK
Fan-and-filter unit,
RAL 7035
–
3240.100 3240.110 3240.124 3241.100 3241.110 3241.124
EMC fan-and-filter
unit,
RAL 7035
–
3240.600 – – 3241.600 – –
Rated operating
voltage
V
Hz
230, 1~,
50/60
115, 1~,
50/60
24 (DC)
230, 1~,
50/60
115, 1~,
50/60
24 (DC)
Rated current max. A 0.19/0.18 0.38/0.36 0.07 0.27/0.28 0.54/0.52 0.2
Power
consumption
W 33/33 10 42/46 43/46 25
Pre-fuse T A 2 4 2 4 2
Dimensions
B1/H1 mm 255 x 255
B2/H2 mm 224 x 224
T1 mm 25
T2
(max. installation
depth)
mm 107
Air throughput,
unimpeded air flow
m³/h 180/160 180 230/250 230
Air throughput with
outlet filter
including standard
filter mat
m³/h
1 x 3240.200: 138/121 1 x 3240.200: 183/205
2 x 3240.200: 165/140 2 x 3240.200: 203/230
1 x 3243.200: 165/140 1 x 3243.200: 203/230
Outlet filter
–
3240.200
EMC
outlet filter
–
3240.060
Fan –
Diagonal, self-starting
shaded pole motor
Diagonal,
DC motor
Diagonal, self-starting
shaded pole motor
Diagonal,
DC motor
Noise pressure
level
dB (A) 51/46 51 54/56 54
Operating
temperature
°C –30 to +55
Storage
temperature
°C –30 to +70
Protection category
(to EN 60 529)
–
IP 54 standard
IP 55 with additional fine filter mat or hose-proof hood
IP 56 with hose-proof hood
Tab. 4: Technical specifications
We reserve the right to make technical modifications.