Filterlüfter Fan-and-filter unit Ventilateur à filtre Ventilator Filterfläkt Ventilatore-filtro Ventilador con filtro SK 3237.xxx SK 3238.xxx SK 3239.xxx SK 3240.xxx Montage-, Installations- und Bedienungsanleitung Assembly and operating instructions Notice d’emploi, d’installation et de montage Montage- en bedieningshandleiding Montage- och hanteringsanvisning Istruzioni di montaggio e funzionamento Instrucciones de montaje y funcionamiento SK 3241.xxx SK 3243.xxx SK 3244.xxx SK 3245.
Contents 1 Notes on documentation . . . . . . 4 1.1 1.2 1.3 EN 5 Other applicable documents . . . . . . . . . . . . . . . . 4 Storing the documents . . . . . . 4 Symbols used . . . . . . . . . . . . . 4 Carrying out the electrical installation . . . . . . . . . . . . . . . . . 9 5.1 5.2 5.3 2 Safety notes . . . . . . . . . . . . . . . . 5 3 Device description . . . . . . . . . . . 5 3.1 3.1.1 3.1.2 3.1.3 3.1.4 3.2 3.3 4 Functional description . . . . . . 5 How it works . . . . . . . . . . . . . . .
1 Notes on documentation EN 1 Notes on documentation 1.3 Symbols used These assembly instructions are aimed at tradespersons who are familiar with assembly and installation of the fan-and-filter unit, and at trained specialists who are familiar with operation of the fan-and-filter unit. Please observe the following safety instructions and other notes in this guide: Symbol for an instructed action: • The bullet point indicates that you should perform an action. Safety and other notes: 1.
2 Safety notes 2 Safety notes 3 Device description Please observe the following general safety notes when assembling and operating the unit: – Assembly, installation and servicing may only be performed by properly trained specialists. – Do not obstruct the air inlet and outlet of the fan-and-filter unit inside and outside the enclosure (see also section “4.2.2 Layout of the components in the enclosure”, page 7).
3 Device description EN 3.1.2 Control Rittal fan-and-filter units may be controlled more efficiently using a thermostat (Model No. SK 3110.000), digital temperature display (Model No. SK 3114.200), temperature-dependent speed control (Model No. SK 3120.200) and/or hygrostat (Model No. SK 3118.000). Control unit (Model No. SK 3235.440) for fan-and-filter unit SK 3245.xxx only. 3.1.
4 Assembly and connection 4 Assembly and connection 4.1 Choosing the installation site When choosing the installation site for the enclosure, please observe the following: – The site for the enclosure, and hence the arrangement of the fan-and-filter unit, must be carefully selected so as to ensure good ventilation. – The site must be free from excessive dirt and moisture. – The ambient temperature must be lower than the permissible enclosure interior temperature.
4 Assembly and connection 4.4 Notes on electrical installation EN Fig. 2: SK 3237.xxx SK 3238.xxx When performing the electrical installation, it is important to observe all valid national and regional regulations as well as the provisions of the responsible power supply company. Electrical installation must only be carried out by a qualified electrician who is responsible for compliance with the existing standards and regulations. SK 3239.xxx SK 3240.xxx SK 3241.xxx SK 3243.xxx SK 3244.xxx SK 3245.
5 Carrying out the electrical 5 Carrying out the electrical installation fan. Units SK 3238.xxx to SK 3239.xxx are released by pulling out the clip (see Fig. 4) of the bayonet connection. 5.1 Installing the power supply EN SK 3238.xxx SK 3239.xxx • Complete the electrical installation by following the wiring plans. Note: For technical data refer to the rating plate. • Remove the red cover from the electrical connection. Fig. 4: Release the bayonet connection Units SK 3240.xxx, SK 3241.xxx, SK 3243.
6 Commissioning EN 6 Commissioning • Once all the assembly and installation work is complete, switch on the power supply to the fan-and-filter unit. The fan-and-filter unit operates automatically, in other words, the fan will start up once the power has been switched on. 6.1 Properties – Four voltage variants are supported: – 24 V DC – 115 V, 1~ – 230 V, 1~ – 400/460 V, 3-phase 7 Changing the filter Fig. 6: Release the louvred grille • Insert the filter mat into the louvred grille as shown in Fig.
8 Inspection and maintenance 8 Inspection and maintenance Risk of electric shock! The unit is live. Switch off the power supply before opening, and take suitable precautions against it being accidentally switched back on. 8.1 General The built-in, maintenance-free fan is mounted on a friction bearing (SK 3237.xxx, SK 3238.xxx and SK 3239.xxx) or ball bearing (SK 3240.xxx, SK 3241.xxx, SK 3243.xxx to SK 3245.xxx), and is protected against humidity and dust, and equipped with a temperature monitor.
10 Technical specifications EN 10 Technical specifications – Observe the pre-fuse as per the specifications on the rating plate. – Observe the mains connection data (voltage and frequency) as per the rating plate. Unit Model No. SK Fan-and-filter unit, RAL 7035 – 3237.100 3237.110 3237.124 3238.100 3238.110 3238.124 EMC fan-and-filter unit, RAL 7035 – 3237.600 – – 3238.
10 Technical specifications Unit Model No. SK Fan-and-filter unit, RAL 7035 – 3239.100 3239.110 3239.124 EMC fan-and-filter unit, RAL 7035 – 3239.600 – – Rated operating voltage V Hz 230, 1~, 50/60 115, 1~, 50/60 24 (DC) Rated current max. A 0.12/0.11 0.24/0.23 0.28 Power consumption W 19/17 Pre-fuse T A 2 EN 6 Dimensions B1/H1 mm 204 x 204 B2/H2 mm 177 x 177 T1 mm 24 T2 (max.
10 Technical specifications EN Unit Model No. SK Fan-and-filter unit, RAL 7035 – 3240.100 3240.110 3240.124 3241.100 3241.110 3241.124 EMC fan-and-filter unit, RAL 7035 – 3240.600 – – 3241.600 – – Rated operating voltage V Hz 230, 1~, 50/60 115, 1~, 50/60 24 (DC) 230, 1~, 50/60 115, 1~, 50/60 24 (DC) Rated current max. A 0.19/0.18 0.38/0.36 0.07 0.27/0.28 0.54/0.52 0.
10 Technical specifications Unit Model No. SK Fan-and-filter unit, RAL 7035 – 3243.100 3243.110 3244.100 3244.110 3244.140 3245.500 3245.510 EMC fan-andfilter unit, RAL 7035 – 3243.600 – 3244.600 – – EN 3245.600 – Rated operating voltage V Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60 400/460, 230, 3~, 1~, 50/60 50/60 115, 1~, 50/60 Rated current max. A 0.37/ 0.43 0.75/ 0.80 0.59/ 0.81 1.0/ 1.4 0.22/ 0.24 1.3 2.
11 Cut-out/drilling dimensions 11 Cut-out/drilling dimensions B2 T2 H2 T1 B = Width T = Depth H1 EN B1 Fig. 8: Cut-out dimensions Model No. SK Ø mm F mm 3237.xxx 3.5 100.5 3238.xxx 3.5 132.5 3239.xxx 4.5 185 3240.xxx 4.5 234 3241.xxx 4.5 234 3243.xxx 4.5 302 3244.xxx 4.5 302 3245.xxx 4.5 302 Tab. 6: Drilling dimensions Fig.
12 EMC fan/outlet filter 12 EMC fan/outlet filter EN To achieve EMC protection, the EMC fans and EMC outlet filters should be snapped into the mounting cut-out and screwfastened using the supplied screws. Next, the four contact foils should be stuck on all-round between the fan-and-filter unit and the inside of the enclosure as shown in the following illustration. Fig. 10: EMC contact foils Note: Only use original EMC filter mats (see Accessories in the Rittal Catalogue).
13 Connection diagrams EN 13 Connection diagrams M 1~ M 1~ L N PE 3237.100/.110/.600 3238.100/.110/.600 3239.100/.110/.600 L PE 3243.100/.110/.600 3244.100/.110/.600 M 1~ L N M 1~ M 3~ N PE 3240.100/.110/.600 3241.100/.110/.600 L1 L2 L3 PE 3244.140 L N P 3245.500/.510/.600 For details, see page 19 M 24 V DC – 24 + 3237.124 3238.124 3239.124 3240.124 3241.124 Fig.
13 Connection diagrams For SK 3245 only! 1 EN 2 Fan/motor Interface 3 2 CON10 2 1 10 V 1V <1 V L N 1 – 10 V n = max. n = min. n=0 1.6 AT CON11 AC 1 P AC 2 N PE CON12 PE 1 +10 V 3 3 4 I max. = 1.1 mA 15 V 1 3 2 4 10 V/PWM 2 47 k 3 I max. = 10 mA 47 k 1 uF GND 1 2 10 K 2 Speed 4 12 V 1 100 % PWM 10 % PWM <10 % PWM 1 680 R 3 1 4 2 ZMM 47 n = max. n = min. n=0 Fig. 12: Connection diagram SK 3245 1 Max.
14 EC declaration of conformity EN 14 EC declaration of conformity 20 Rittal fan-and-filter unit assembly and operating instructions