Specifications

Technical Specifications
UPS-Manual
30
EN
Environmental
Operation Temperature* 0 - 40 °C
Noise Level < 50 dBA
Relative Humidity 0 to 90% (Without condensation)
Interface
Interface Type 1x USB port, 1x RS-232 port, 1x Slot for Communication Card
SNMP Power management from SNMP manager and Web browser
Compatible platforms Windows 95/98/NT/2000/XP/Vista, Novell NetWare, Linux, etc.
Standards and Certification
Safety IEC/EN 62040-1-1,IEC 60950-1
Performance IEC/EN 62040-3
EMC
IEC/EN62040-2 Class A, FCC Part 15 Subpart B Class A,
IEC/EN55011, CISPR11, IEC61000-4-2/-3/-4/-5, IEC61000-2-2,
IEC61000-3-2/-3
Markings CE, WEEE
*NOTE: Is the UPS running in an environment with temperatures over 40°C this will lead to a
clear shortened life-time of the batteries. In some cases this can cause damage on the batteries
and the UPS.
Model 1KVA 2KVA 3KVA
Backup Time with Extended Battery Module
Load
100% >28min. >17min. >12min.
80% >35min. >24min. >17min.
60% >55min. >32min. >24min.
40% >110min. >50min. >37min.
1 extended Battery
module
20% >155min. >105min. >88min.
Load
100% >55min. >29min. >20min.
80% >68min. >38min. >26min.
60% >96min. >51min. >35min.
40% >144min. >86min. >58min.
2 extended Battery
modules
20% >300min. >175min. >127min.