10. Technical Specifications
Model 1KVA 2KVA 3KVA
VA Rating
Apparent Output Power 1000VA 2000VA 3000VA
Active Output Power
800 Watts 1600 Watts 2400 Watts
Power Factor
0,8
Topology
Double conversion On-Line
Type Rack/Tower
Agency Approvals 230V Models: CE
Input
Voltage Window 230V 120/140/160 - 288Vac
Base on load percentage (0~33/33~66/66~100%)
Low Line
Transfer
230V 120/140/160Vac
Low Line
Comeback
230V
170Vac
High Line
Transfer
230V 288Vac
Voltage
Range
High Line
Comeback
230V 278Vac
Frequency 50/60 Hz auto-select, ± 5Hz
Phase Single phase with ground
PF > 0,99 at full rated linear load
Typical Transfer Time 0 ms
AC Leakage current 230V
≤ 3,5mA
Surge Protection 230V 300 joules
Output
Voltage 230V 230V,adjustable to 220/230/240
Voltage
Regulation
≤± 1% until low battery warning
Frequency(Synchr
onized Range)
3Hz or 1Hz (setting by software)
Frequency(Battery
Mode)
±0,1% (0,05~0,06Hz) unless synchronized to line
Output
(INV.
mode)
Current Crest
Factor
3:1