Installation manual
Rinnai Australia 23 Installation Manual
FLUE INSTALLATION
For all installations, only “Abey
®
” Flue components shown in these instructions MUST BE used. This
appliance MUST NOT be flued into ‘natural draft’ flue system or terminate into a chimney.
All measurements are in (mm)
Correct baffle must be used for vertical installations refer to page 28 for details.
Max 5400
Min Vertical
Rise 600
Max 800
Min 300
Only one 90° change
of direction allowed on
any installation.
For horizontal flue
installations no baffle
plate is required
Vertical
Flue
Installation
Vertical
Offset Flue
Installation
Horizontal
Flue
Installation
For vertical and vertical offset
flue installations a baffle plate
will need to be fitted
Total Flue length not to
exceed 5400
500
CAUTION
FLUE INSTALLATION CONFIGURATION