Installation manual

Rinnai Australia 35 Installation Manual
HEATER INSTALLATION
Step 5. CONNECT FLUE AND INSTALLING THE FLUE RESTRICTOR
Connect the Abey® Flue to the flue outlet at the top of the appliance.
A flue restrictor is required for Vertical and Vertical Off-set installations.
If a flue restrictor is required install as follows:
Step 1. Remove the pilot cover panel by tilting up and back and lifting out from its location slots.
Step 2). Carefully remove the burner pad assembly by carefully but firmly grasping the burner and lifting in an
upward and forward motion.
Step 3). Fit the flue restrictor choosing the appropriate baffle position. See images below.
Step 4). Carefully replace the burner pad assembly ensuring it locates correctly over the locating tabs fixed to
the base of the burner box.
PLEASE NOTE: Also available in 900mm Flue Length Part No. RDV903
No restrictor installed
(Heater shipped in this state)
For horizontal installations and
vertical / vertical offset flue
installations that do not
exceed 1.8 metres.
Restrictor installed
in position 3
Vertical / vertical offset flue
installations that exceed
3 metres but do not
exceed 4.2 metres.
3 3
1
2
Restrictor Installation
Settings Holes
4
3
1
2
4
3
Restrictor installed
in position 4
Vertical / vertical offset flue
installations that exceed
1.8 metres but do not
exceed 3 metres.
4 4
Restrictor installed
in position 3
For areas of extreme cold
Vertical / vertical offset flue
installations that exceed
4.2 metres & up to 5.4 metres.
3 3
Restrictor installed
in position 2
Vertical / vertical offset flue
installations that exceed
4.2 metres & up to 5.4 metres.
2 2