HE Series Infrared Gas Heater Installation and Operation Manual
: Single or multiple heater placement must be such that continuous
operation of heaters will not cause combustible material or materials in storage to
reach a temperature in excess of ambient (room) temperature plus 117F° (65C°).











(m)
 


(m)

HE Series
8 12
(2.4 - 3.7)
5 12
(1.5 - 3.7)
MINIMUM: COMBUSTIBLE
CLEARANCE BEHIND
12to 24”
(305 to 610 mm)
 
-
* SUGGESTED GUIDELINE MOUNTING HEIGHTS are typical to provide optimum comfort in
general space heating applications. Variance from these typical heights can occur in some
applications:
Higher mounting height due to structure or application requirements
For areaor spotheat, or in areas with greater infiltration rates (near overhead doors,
etc) where more intense heat is needed to provide better comfort then lower mounting
heights are recommended (minimum 8 ft [2.4 m] mounting height)
It is recommended that Protective Guard JS-0502-UR-GK be installed on any heater
mounted with less than 8 feet from floor to bottom of heater (See Accessories - Page 41)