Installation Manual

10
HE Series Infrared Gas Heater Installation and Operation Manual

 either adjacent
to the IR heating system thermostat or in the absence of such thermostat, in a conspicuous
place specifying the required clearances from the heater to the combustibles.

is a value calculated at site: ( = - ) Refer to Figure 1 and Table 1 above
Measure the on site distance between bottom of the heater and the floor = inches (cm).
The minimum clearance to combustibles below this heater is 
Subtract 53 inches (1346 mm) from
(Height above floor) to get value ’.
Enter the calculated value on the sign
Enter the values as required for the other dimen-
sions:
’ = 24” (610 mm)
’= 48” (1120 mm)
’ = 12” (305 mm) at 30°
Or ’ = 24” if mount angle less than 30°

.
24”
12”
48”
WARNING
: Clearance from single wall Cvent pipe inside the building is deter-
mined by local or national installation codes, but must not be less than 6 inches (150 mm).
Clearance from the vent terminal outside the structure are indicated in Section 11 Flue Vent-
ing and Figures 9 to 12, pages 19 to 23 for details and requirements for venting.