TDS
PERFORMANCE DATA ELECTRICAL DIAGNOSTICS
DIAGNOSTIC CODES
#
DATA UNIT
01
Water Flow Rate x0.1 gal/min
02
Outgoing Temperature °F
03
Combuson Hours x100 Hours
04
Combuson Cycles See following informaon
05
Fan Frequency Hz
06
Addional Controllers Connected See following informaon
07
Water Flow Control Posion 0=Mid, 1=Open, 2=Closed
08
Inlet Temperature °F
09
Fan Current x10 mA
10
Total Bath Fill Amount gallons
11
HEX Outlet Temperature °F
12
By-Pass Flow Control Posion Degrees of opening
14
Intake Thermistor Temperature
(Indoor Units Only)
°F
17
Freeze Protecon Temperature
(Outdoor Units Only)
°F
19
Pump Hours x100 Hours
20
Pump Cycles See following informaon
DISPLAY CYCLE COUNT
000 to 999 x100 (0 to 99,900)
10– to 99- x10,000 (100,000 to 990,000)
1-- to 6-- x1,000,000 (1,000,000 to 6,000,000)
2. Use the (Up) and (Down) buon on the controller to select a seng number (See Parameter
Sengs Table).
NOTE: Wiring diagram is available in manual and on the inside front cover.
Important Safety Notes
There are a number of (live) tests required when performing electrical diagnoscs on this
product. Proceed with cauon at all mes to avoid contact with energized components inside the
water heater. Only trained and qualied service technicians should aempt to repair this product.
Before checking for resistance readings, disconnect the power source to the unit and isolate the
item from the circuit (unplug it).
Freeze Protecon
This unit has freeze protecon heaters mounted at dierent points to protect the water heater
from freezing. All of them should display a posive resistance reading.
Flame Rod
Place one lead of your meter to the ame rod and the others to ground. When the unit is
aempng to ignite, you should read more than 0.5 VAC.
Amp Fuses
This unit has two glass fuses located on the PC Board, one inline (10) amp and one (4) amp glass
fuse. Remove the fuses and check connuity through it. If you have connuity through each fuse
then it is funconing. Otherwise the fuse is blown and must be replaced. Note: RE140i/e does not
have a 4 amp fuse.
Thermistors
Check all thermistors by inserng meter leads into each end of the thermistor plug. Set your
meter to the 20 K scale and read resistance. Applying heat to the thermistor bulb should decrease
the resistance. Applying ice to the thermistor bulb should increase the resistance.
Below are examples of typical temperatures and resistance readings.
(* Value to be measured while unit is in operaon)
10
Air Supply or Exhaust Blockage
• Ensure approved venng materials are being used.
•
Check that nothing is blocking the ue inlet or exhaust.
•
Check all vent components for proper connecons.
•
Ensure vent length matches with the vent lengths set in the parameter sengs.
•
Verify High Altude seng is set properly. (See Parameter Seng)
• Check fan for blockage.
1 1
No Ignion (Heater Not Turning On)
•
Check that the gas is turned on at the water heater, meter, or propane cylinder.
•
If the system is propane, make sure that gas is in the tank.
•
Bleed all air from the gas line
•
Ensure appliance is properly grounded.
•
Ensure gas type and pressure is correct.
•
Ensure gas line, meter, and/or regulator is sized properly.
•
Verify parameter seng are set properly.
•
Ensure igniter is operaonal.
•
Check igniter wiring harness for damage.
•
Check gas solenoid valves for open circuits.
•
Ensure ame rod wire is connected.
•
Check ame rod for carbon build-up.
•
Remove burner cover and ensure burners are properly seated.
•
Remove burner plate; inspect burner surface for condensaon/debris.
• Check the ground wire for the PC board.
12
No Flame
•
Check that the gas is turned on at the water heater, meter, or cylinder.
•
Check for obstrucons in the ue outlet.
•
If the system is propane, make sure that gas is in the tank.
•
Ensure gas line, meter, and/or regulator is sized properly.
•
Ensure gas type and pressure is correct.
•
Bleed all air from gas lines.
•
Ensure proper venng material was installed.
•
Ensure condensaon collar was installed properly.
•
Ensure vent length is within limits.
•
Verify parameter seng are set properly.
•
Check power supply for loose connecons.
•
Check power supply for proper voltage and voltage drops.
•
Ensure ame rod wire is connected.
•
Check ame rod for carbon build-up.
•
Disconnect and reconnect all wiring harnesses on unit and PC board.
•
Check gas solenoid valves for open circuits.
• Remove burner plate; inspect burner surface for condensaon/debris.
14
Thermal Fuse
•
Check for restricons in air ow around unit and vent terminal.
•
Check gas type of unit and ensure it matches gas type being used.
•
Check for low water ow in a circulang system causing short-cycling.
•
Check for foreign materials in combuson chamber and exhaust piping.
•
Check heat exchanger for cracks or separaons.
•
Check heat exchanger surface for hot spots which may be caused by scale build-up.
Refer to instrucons in manual for ushing heat exchanger. Hard water must be
treated to prevent scale build up or damage to the heat exchanger.
•
Measure resistance of safety circuit.
•
Ensure high re and low re manifold pressure is correct.
• Check for improper gas conversion of product.
16
High Outgoing Temperature
•
Check for restricons in air ow around unit and vent terminal.
•
Check for low water ow in a circulang system causing short-cycling.
•
Check for foreign materials in combuson chamber and exhaust piping.
•
Check for blockage in the heat exchanger.
• Check the thermistor sensor and clean sensor of scale build-up.
19
Electrical Grounding
• Check all components for electrical short.
32
Outgoing Water Temperature Thermistor
• Check sensor wiring for damage.
• Measure resistance of sensor. (See Electrical Diagnoscs)
• Clean sensor of scale build-up.
• Replace sensor if necessary.
33
Heat Exchanger Thermistor
• Check sensor wiring for damage.
• Measure resistance of sensor. (See Electrical Diagnoscs)
• Replace sensor if necessary.
34
Combuson Air Temperature Thermistor Fault
•
Check for restricons in air ow around unit and vent terminal.
•
Check sensor wiring for damage.
•
Measure resistance of sensor.
•
Ensure fan blade is ght on motor sha and is in good condion.
• Replace sensor if necessary.
41
Freeze Protecon Thermistor
•
Check sensor wiring for damage.
•
Measure resistance of sensor. (See Electrical Diagnoscs)
• Replace sensor if necessary.
51
Inlet Water Temperature Thermistor
•
Check sensor wiring for damage.
•
Measure resistance of sensor. (See Electrical Diagnoscs)
• Replace sensor if necessary.
52
Modulang Solenoid Valve Signal
•
Check modulang gas solenoid valve wiring harness for loose or damaged terminals.
• Measure resistance of valve coil.
61
Combuson Fan
•
Ensure fan will turn freely.
•
Check wiring harness to motor for damaged and/or loose connecons.
• Measure resistance of motor winding.
63
Recirculaon Low Flow
•
Ensure the inlet water lter is clean and free of debris.
•
Ensure parameter seng are correctly set for recirculaon mode.
•
Ensure pump supply voltage.
•
Check the wiring harness to the pump and PCB for damaged and/or loose
connecons.
• Ensure air is removed from the recirculaon line.
65
Water Flow Servo
•
Measure the resistance values and voltage of the water ow control.*
•
Ensure the harness and connector are not wet.
• If the voltage from the PC Board is abnormal, replace the PC Board; otherwise,
replace the water ow servo valve.
66
Bypass Flow Servo
•
Measure the resistance values and voltage of the bypass servo valve.*
•
Ensure the harness and connector are not wet.
• If the voltage from the PC Board is abnormal, replace the PC Board; otherwise,
replace the bypass servo valve.
70
PC Board
•
Check the connecon harness at the connecon on the PC board.
• Replace PC board.
71
Solenoid Valve Circuit
•
Ensure dip switch on PC board is in the OFF posion.
•
Check gas solenoid valves for short circuits or grounding.
•
Ensure heater circuit is not grounded.
• Replace PC Board.
72
Flame Sensing Device
•
Verify ame rod is touching ame when unit res.
•
Check the ame rod and wire for damage.
•
Remove ame rod;check for carbon build-up; clean with sand paper.
•
Check inside burner chamber for any foreign material blocking ame at ame rod.
•
Check the resistance to the cabinet.
• If there is no issue with the ame rod or wiring, replace the PC Board.
79
Water Leak Detected
•
Turn o water supply and contact licensed professional.
LC
Scale Build-up in Heat Exchanger (when checking maintenance code history, “00” is
substuted for “LC”
•
LC indicates that there is scale build up in the heat exchanger and that the heat
exchanger needs to be ushed to prevent damage. Refer to the ushing instrucons
in the manual. Hard water must be treated to prevent scale build up or damage to
the heat exchanger.
•
Aer ushing, reset LC code as instructed.
•
Please call Rinnai technical department.
ss
(SS) Service Soon (Flush Heat Exchanger)
•
SS
is a me-based service indicator set during installaon. See secon “4.10
Congure Parameter Sengs” for addional details on seng and changing the
SS
indicator.
•
SS
indicates that it is me for service. The heat exchanger should be ushed to
prevent damage (refer to secon “6.2 Flushing the Heat Exchanger” for more
informaon). Hard water must be treated to prevent scale build-up or damage to
the heat exchanger.
•
To reset the
SS
code, push the On/O buon on the temperature controller 5 mes
in 5 seconds.
NO CODE - Nothing happens when water ow is acvated
•
Clean inlet water supply lter.
•
On new installaons ensure hot and cold water lines are not reversed.
•
Verify you have at least the minimum ow rate required to re unit.
•
Check for cold to hot cross over. Isolate circulang system if present. Turn o cold
water to the unit, open pressure relief valve; if water connues to ow, there is
bleed over in your plumbing.
•
Verify turbine spins freely.
•
Measure the resistance of the water ow control sensor.
•
If the display is blank and clicking is coming from the unit, disconnect the water
ow servo motor (GY, BR, O, W, P, BL, R). If the display comes on then replace the
water ow servo motor.
FF
Maintenance Indicator
A
B
PARAMETER SETTINGS
Performance Data Table
Electrical Circuit Table
Temperature Resistance Readings
59°F 11.4 - 14KΩ
86°F 6.4 - 7.8KΩ
113°F 3.6 - 4.5KΩ
140°F 2.2 - 2.7KΩ
221°F 0.6 - 0.8KΩ
1
2
CONTROLLER MODEL CONNECTED NOT CONNECTED
MC
__1 __0
BC
_1_ _0_
BSC & BSC2 1__, 2__ (QTY2)
0__
Default display is
100.
_
depends on connecon status of another controller.
06
Controllers Connected
04
Combuson Cycles
20
Pump Cycles
To Display Diagnosc Codes:
1. Turn o the water heater by pressing the “On/O” buon.
2. Press and hold the “On/O” for 2 seconds and then the (Up) buon simultaneously.
3. The last 9 maintenance codes display and ash one aer the other.
4. To exit diagnosc codes and return the water heater to normal operaon, press and hold the “On/O” buon for 2 seconds and then
the (Up) buon simultaneously.
5. Turn on the water heater by pressing the “On/O” buon.
1
2
1
3
FF
3
3
1
2
2
3
U356-0755-1X02(00)
100000733
Parameter Sengs Table
SETTING
#
SETTING
DESCRIPTION
SELECTION
A
c
01
Maximum Set
Temperature
120°F 140°F
02
High Altude
(Installaon Locaon)
0 - 2,000
(0 - 610 m)
2,001 - 5,400
(610 - 1,646 m)
5,401 - 7,700
(1,646 - 2,347 m)
7,701 - 10,200
(2,347 - 3,109 m)
03
Service Soon
Disabled 0.5 Year 1 Year 2 Years
04
Recirculaon Sengs No Recirculaon
Recirculaon
(Dedicated)
05
Recirculaon Mode Economy Comfort
06
Control Switch
BMS
Air Handler (AH)
07
Units in Standby
2 1
10
Gas Type
(Factory Set)
LPG NG
12
Water Heater Model
(Factory set values and
not adjustable)
Without Pump With Pump
13
199/160 180/140
14
Indoor Outdoor
15
Low Acvaon Mode
On O
18
Seng Temperature
Table
Default Alternate
19
Adjust DHW
Temperature Seng
0°F (0°C) 1.8°F (1°C) 3.6°F (2°C) 5.4°F (3°C)
99
Vent Length
Long Short
Visit www.rinnai-lms.com for addional troubleshoong resources
2
Rinnai America Corporaon connually updates materials, and as such, content is subject to change without noce. For further informaon, contact Rinnai at 1-800-621-9419 or visit www.rinnai.us
To Obtain Performance Data:
1. Press and hold the (Down) buon.
2. While holding the (Down) buon for 2 seconds, press and hold the “On/O”
buon (hold both buons simultaneously).
3. Use the (Up) and (Down) buons to scroll to the desired performance
informaon described below.
01A
01
To Adjust the Parameters:
1. Press the “A” buon for 1 second.
3. Once the desired seng number is selected, use the “On/O” buon on the
controller to change the selecon for the seng number.
Example: Display will change from 01A to 01b for Maximum Temperature seng
(as shown below).
4. To exit the parameters, press the “A” buon on the PC board for 1 second.
MANIFOLD PRESSURE SETTINGS
Ensure gas pressure check under Commissioning has been completed rst! The regulator is
electronically controlled and factory pre-set. Under normal circumstances it does not require
adjustment during installaon. Make adjustments only if the unit is not operang correctly and
all other possible causes for incorrect operaon have been eliminated.
1. Turn o the gas supply.
2. Turn o the 120 V power supply.
3. Remove the front panel from the appliance.
4. Turn on the 120 V power supply.
5. Check the gas type using the data plate on the side of the unit and parameter seng 10
(refer to Parameter Sengs secon). (A=LPG, b=NG).
6. Remove test port screw and aach the manometer to the burner test point, located on
the manifold.
7. Turn on the gas supply.
8. Flow water through the water heater at the maximum ow rate obtainable. (At least 3
gallons per minute is recommended. If there is not enough water owing, the water
heater could shut o or sustain damage due to overheang.)
9. Push and hold “B” buon. “IF” will appear on the display.
10. Push and hold “A” buon. “Forced Low” will appear on the display.
11. Push and hold “A” buon again. “Forced High” will appear on the display.
12. While in “Forced Low” or “Forced High”, use the Up buon on the controller to increase
the pressure. Use the Down buon to decrease the pressure.
13. To exit “Forced Low” or “Forced High”, push and hold “B” buon. “2L” will appear on the
display.
14. Push and hold “B” buon again. “3C” will appear on the display. (Indoor models only).
15. Push and hold “B” buon again. “4t” will appear on the display.
16. Push and hold “B” buon again. The set temperature will appear on the display (indoor
models only).
17. Close hot water taps.
18. Turn o the gas supply and 120 V power supply.
19. Remove the manometer and re-install the sealing screw.
20. Turn on the gas supply and 120 V power supply.
21. Operate the unit and check for gas leaks.
22. Install the front panel.
Note: For addional installaon and commissioning informaon, refer to the Installaon and Operaon
Manual.
This appliance must be installed, serviced and removed by a trained and
qualied person. During pressure tesng of the consumer piping, ensure gas
valve is turned o before unit is shut o. Failure to do so may result in serious
injury to yourself or damage to the unit.
WARNING
Commissioning
With all gas appliances in operaon at maximum gas rate, the following inlet gas pressure at the incom-
ing test point on the Rinnai water heater should read 4 in. wc - 10.5 in. wc on natural gas and 8 in. wc -
13.0 in. wc on propane gas. If the pressure is lower, the gas supply is inadequate and the unit will not
operate to specicaon. Check the gas meter regulator and pipework for correct operaon/sizing and
correct as required.
Model
#
Vent
Length
Maximum
Water
Pressure
Gas Supply Pressure
Min./Max.
(FL) Forced Low (FH) Forced High
NG LPG NG LPG
NG LPG inH2O(wc) inH2O(wc) inH2O(wc) inH2O(wc)
RE199i
Short
150 PSI 4.0/10.5 8.0/13.0
0.72 0.98 2.56 4.24
Long 0.71 1.00 2.39 3.92
RE180i
Short 0.72 0.98 2.56 4.24
Long 0.71 1.00 2.39 3.92
RE160i
Short 0.73 0.96 2.49 4.31
Long 0.74 0.96 2.55 4.48
RE140i
Short 0.73 0.96 2.49 4.31
Long 0.74 0.96 2.55 4.48
COMPONENT WIRE COLOUR VOLTAGE RESISTANCE
PCB
Connector PIN
Power Supply Black-White
AC108~132V
N/A CN100 1-3
Flame Rod
Yellow-Body more than 0.5VAC N/A CN9 37
Pink-Body more than 0.5VAC N/A CN7 1
Spark Electrode White-Black
11~14VDC*
N/A CN9 5-8
Combuson Fan
Red-Black
7~48VDC*
N/A CN9 1-3
White-Black
2~14VDC*
N/A CN9 2-3
Yellow-Black
11~14VDC
N/A CN9 4-3
Water Flow
Control Device
Red-Pink
N/A
40~60Ω
CN9 21-19
Blue-White CN9 25-23
Orange-Grey
11~14VDC
N/A CN9 6-13
Brown-Grey
limier On:less than 1VDC
limier O:4~6VDC
N/A CN9 17-13
By-Pass Flow
Control Device
(2737, 2432 mod-
el only)
Red-Pink
N/A
40~60Ω
CN9 29-27
Blue-White CN9 33-31
Main Solenoid
Valve
Black-Black
8~13.5VDC 15~25Ω
CN9 18-32
Modulang
Solenoid Valve
Yellow-Yellow
2~17VDC* 10~20Ω
CN9 12-14
Solenoid Valve 1 Blue-Black
8~13.5VDC 20~30Ω
CN9 24-22
Solenoid Valve 2 Yellow-Black
8~13.5VDC 20~30Ω
CN9 26-22
Solenoid Valve 3 Red-Black
8~13.5VDC 20~30Ω
CN9 28-22
Solenoid Valve 4
(2737, 2432, 2730
model only)
Orange-Black
8~13.5VDC 20~30Ω
CN9 30-22
Outgoing Water
Thermistor
White-White
N/A
59°F:11.4-14kΩ
86°F:6.4-7.8kΩ
113°F:3.6-4.5kΩ
140°F:2.2-2.7kΩ
221°F:0.6-0.8kΩ
Disconnect the con-
nector and measure
at thermistor side.
CN7 11-13
White-White CN7 4-5
Inlet
Thermistor
White-White CN7 9-6
Heat Exchanger
Thermistor
White-White CN7 8-4
Intake
Thermistor
(Indoor type only)
White-White CN7 12-6
Freeze
Protecon
Thermistor
(Outdoor type
only)
White-White
32°F:38k-43k
50°F:22k-26k
CN7 10-6
Overheat Switch Black-Black less than 1VDC less than 1Ω CN9 10-16
Water Flow
Sensor
Red-Black
11~14VDC
N/A
CN9 7-11
Yellow-Black
4~7VDC*
Comment:more than 6Hz
(1.0L/min)
CN9 9-11
Integrated Pump
(Integrated Pump
type only)
White-Black
AC108~132V
N/A C101 1-2
Red-Brown
11~14VDC*
N/A CN8 1-2
External Pump
(Except for inte-
grated pump and
1720 model)
White-Black
AC108~132V*
N/A C101 1-2
Addional
Controller(s)
White-White
11~14VDC
N/A CN4 1-3
Thermal Fuse White-White
less than 1VDC less than 1Ω CN9 20-34
•
Placeholder in Diagnosc code history indi-
cang that a service provider performed
maintenance or service.
•
Enter this code aer performing service by
pressing
(Up) ,
(Down) and On/O
simultaneously.
•
FF
is visible on the monitor.
*See “Electrical Diagnoscs”
(I)


