General Requirements (All Systems):
Return Pump:
A secondary or building return pump must be installed in conjunction with the Rinnai HEX250
High Efficiency Heat Exchange system. Pumps should be sized for minimal temperature loss
around the ring-main. Pumps must have a isolation valve on the discharge.
Return line from building loop is connected to a tee on the cold water supply pipe down stream
of the cold water non return valve.
Gas Supply:
Refer to the operational/installation manual supplied with the HD200 appliance for full details. Some
key points are:
Check gas type of Rinnai HD200 units matches gas type available (LPG or NG) on job site.
Gas inlet connection is located on the top pipe on a manifold pack or RHS connection on a
single HD200.
Appropriate gas isolation valves to be fitted. Manifold pack includes a gas isolation valve for
each unit.
Ensure gas pipe sizing is adequate to deliver the required volume / pressure. Pipe size used on
inlet fitting is no indication of pipe size required.
Refer to pipe sizing chart in Appendix "F" AS/NZS 5601 for appropriate sized gas pipe to be
used to ensure adequate gas supply.
Gas meter / LPG cylinder & regulator must also be of a suitable size outlet and pressure rating
to ensure sufficient gas supply to the gas installation.
Purge gas pipe to ensure removal of debris etc prior to final connection.
Check for gas escapes using suitable methods as listed in Appendix "E" AS/NZS 5601.
Flueing and clearance requirements for HD200i:
For detailed instructions on clearances refer to AS/NZS 5601 Figure 6.2 and flueing requirements for
HD200i units (where necessary) refer to the flue instructions packed separately with the flueing
components.
DDHEX250 Hot Water Thermostat and Electrics:
Each HD200 requires a GPO.
DD250HEXHWTSTAT requires a GPO.
Ring main pumps require a GPO.
Skid packages may include GPO’s, reducing number of GPO’s required in plant room.
The Primary pump is powered and switched by the GPO located on the
thermostat housing.