Specification Sheet

Rinnai Corporation • 103 International Drive • Peachtree City, GA 30269 • Toll-Free: 1-800-621-9419 • Fax: 678-829-1666 • www.rinnai.us
4 SP-CV-02 (2/13)
COMMON VENT SYSTEM
Parts / Kits
Rinnai PN Description Ø Diameter Length/Other
790020 CVent Extension, D8 x L18 8" 18"
790021 CVent Extension, D8 x L39 8" 39"
790022 CVent Elbow D8 x 45degree (2 in a box) 8" 45°
790023 CVent Elbow D8 x 90degree 8" 87°
790024 CVent 8-in Brackets 8"
790025 Centrocerin lubricant
790035 CVent Extension, D4 x L18 4" 18"
790028 CVent Extension, D4 x L39 4" 39"
790029 CVent Elbow D8 x 90degree Vertical Support 8"
790030 CVent 8-in Chase Cover 8"
790031 CVent 8-in Vent Distancer, stainless steel 8"
790034 CVent 8-in Vent Rain Cap 8"
790032 Inverter Coupling Kit with condensate trap 8"
780037 Combustion Air PVC Adapter Kit 8"
Number of
water
heaters
Percent
De-rated
Total BTU Rate
Manifold Pressure
Btu’s at
Minimum Rate
(without MSB)
Btu’s at
Minimum Rate
(with MSB)
Maximum
Rate “W.C.
Minimum
Rate “W.C.
1 0% 199,000 3.0 0.42 15,200
15,200
2 1% 394,000 3.1 0.42 30,400
3 1.5% 588,000 3.1 0.42 45,600
4 2% 780,000 3.1 0.42 60,800
5 2.5% 970,000 3.2 0.45 76,000
6 3% 1,158,000 3.2 0.45 91,200
7 3.5% 1,344,000 3.2 0.45 106,400
8 4% 1,528,000 3.2 0.45 121,600
Water heaters using CVent will automatically de-rate according to the table below.
Maximum Equivalent Vent Length
Number of water
heaters
Minimum Equivalent Vent Length Maximum Equivalent Vent Length
Exhaust* Intake* Exhaust* Intake*
1 to 7 5 ft 15 ft 100 ft 100 ft
8 5 ft 15 ft 41 ft 41 ft
When determining equivalent exhaust and intake vent
lengths add:
6 feet for each 90° elbow
3 feet for each 45° elbow
3 feet for the termination
Add any vent extension lengths which are added
within the header due to increased spacing of the
water heaters
Header kits have already been counted and do
not need to be added.
*Approved exhaust and intake diameter is 8 inches.
De-Rate