Over Temperature Warning
(Safety shutdown because unit is too
hot)
Check for restrictions in air flow around
unit and vent terminal.
Check for low water flow in a circulating
system causing short-cycling.
Check for foreign materials in
combustion chamber and/or exhaust
piping.
Check for blockage in the heat
exchanger.
19
Electrical Grounding
Check all components for electrical
short.
32
Outgoing Water Temperature Sensor
33
Heat Exchanger Outgoing Temperature
Sensor
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.
34
Combustion Air Temperature Sensor
Check for restrictions in air flow around
unit and vent terminal.
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Ensure fan blade is tight on motor shaft
and is in good condition.
Replace sensor.
51
Inlet water temperature thermistor
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.
52
Modulating Solenoid Valve Signal
Check modulating gas solenoid valve
wiring harness for loose or damaged
terminals.
Measure resistance of valve coil.
12
No Flame
Check that the gas is turned on at the
water heater, gas meter, or cylinder.
Check for obstructions in the flue outlet.
If the system is propane, make sure that
gas is in the tank.
Ensure gas line, meter, and/or regulator
are sized properly.
Ensure gas type and pressure are
correct.
Bleed all air from gas lines.
Ensure proper venting material was
installed.
Check power supply for loose
connections.
Check power supply for proper voltage
and voltage drops.
Ensure flame rod wire is connected.
Check flame rod for carbon build-up.
Disconnect and reconnect all wiring
harnesses on unit and PC board.
Check for DC shorts at components.
Check gas solenoid valves for open or
short circuits.
Remove burner plate and inspect burner
surface for condensation or debris.
14
Thermal Fuse has activated
Check for restrictions in air flow around
unit and vent terminal.
Ensure dip switches are set to the proper
position.
Ensure dip switch 5 in the second bank
of dip switches (white) is in the off
position.
Check gas type of unit and ensure it
matches gas type being used.
Check for low water flow in a circulating
system causing short-cycling.
Check for foreign materials in
combustion chamber and/or exhaust
piping.
Check heat exchanger for cracks and/or
separations.
Check heat exchanger surface for hot
spots which indicate blockage due to
scale build-up. Refer to instructions in
manual for flushing heat exchanger.
Hard water must be treated to prevent
scale build up or damage to the heat
exchanger.
Measure resistance of safety circuit.
Ensure high fire and low fire manifold
pressure is correct.
Check for improper conversion of
product.