For the table below:
Header is the main vent pipe into which sev-
eral vents connect
Vent Length is the distance from the end of
the header to the vent termination.
Maximum vent length starts at the end of the
header system.
Use 10 ft (3 m) as equivalent vent length for
90° elbows.
Header
Vent Length
Common Vent Maximum Equivalent Vent Length
Rinnai Common Vent System or Schedule 40 PVC/CPVC
Water Heater
Model
# Water
Heaters
Max
System
BTU/HR
HEADER DIAMETER
3 in. 4 in. 6 in.
3 in.
Vent
Diameter
4 in.
Vent
Diameter
6 in.
Vent
Diameter
6 in.
Vent
Diameter
2 398,000 65
150
150
150
CU199i
(REU-N3237FFC-US)
3 597,000
4 796,000 65
5 995,000
6 1,194,000
7 1,393,000 70
8 1,592,000
CU160i
(REU-N2530FFC-US)
2 320,000 90  150
150
150
3 480,000 100
4 640,000 65
5 800,000
6 960,000
RU130i
(REU-N2024FF-US)
2 260,000 90  150
150
150
3 390,000 100
4 520,000 65
5 650,000
6 780,000
Figure 38