Installation Guide
Polypropylene (PP) Common Venting Installation Instructions            29 
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.  
Installaon Instrucons (Condensate) 
Install the Condensate Trap and Drain Pipe 
The exhaust header collects condensate. A collector and 
self-priming trap is included with each starter kit.  
Condensate must be drained to prevent the malfuncon, 
diagnosc code failures, or property damage. Condensate 
should be disposed according to local codes. Refer to the 
Naonal Fuel Gas Code, ANSI Z223.1/NFPA 54, or the 
Natural Gas and Propane Installaon Code, CSA B149.1 
condensate disposal. 
A condensate pump must be used if the condensate outlet 
is lower than the public sewage system.  
Rinnai recommends installing a condensate neutralizer 
which allows condensate to ow through neutralizing 
media to raise the pH of the condensate to a level that will 
help prevent corrosion of the drain and public sewer system. 
Ensure that the condensate drain does not freeze.  
Ubbink 
condensate 
trap installed 
on exhaust 
Final Checklist 
□  Reference the Rinnai Water Heater Installaon 
and Operaon Manual for proper installaon of 
the Rinnai water heaters. 
□  Clearances from the water heater unit are met.  
□  Clearances from the exhaust terminaon(s) and 
the combuson air terminaon(s) are met. 
□  Ensure you have used the correct venng 
products and that you have completely followed 
the venng manufacturer’s installaon 
instrucons and these installaon instrucons. 
□  Verify that the vent system does not exceed the 
maximum equivalent length allowed. 
□  Explain to the customer the importance of not 
blocking the vent terminaon or air intake. 
□  Explain to the customer the operaon of the 
water heater, safety guidelines, maintenance, 
and warranty. 
□  The installaon must conform with local codes 
or, in the absence of local codes, with the 
Naonal Fuel Gas Code, ANSI Z223.1/NFPA 54
, or 
the 
Natural Gas and Propane Installaon Code, 
CSA B149.1
. 
□  Inform the consumer if the isolaon valves are 
not installed or if a water soening system is not 
installed. 
□  Verify that the water heaters installed match the 
model numbers described in the manual. 
□  Verify that the appropriate amount of 
combuson air has been provided. 
□  Verify the parameter seng has been adjusted 
for the altude/elevaon of the installaon 
locaon. 
□  Leave this manual taped to one of the water 
heaters or give the enre manual directly to the 
consumer. 