Installation Guide
Polypropylene (PP) Common Venting Installation Instructions            23 
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.  
Exhaust Vent Terminaon Clearances 
Direct Vent for indoor models, you must install terminaons to bring in combuson air and expel exhaust 
SNOW
TERMINATION
Clearance in
Ref. A also
applies to
anticipated
snow line
  AIR SUPPLY INLET 
VENT TERMINAL 
AREA WHERE TERMINAL 
IS NOT PERMITTTED 
X
V
Clearance to opposite wall is 24 in. (60 cm).  
[1] A vent shall not terminate directly above a sidewalk or paved driveway 
that is located between two single family dwellings and serves both 
dwellings. 
[2] Permitted only if veranda, porch, deck, or balcony is fully open on a 
minimum of two sides beneath the floor. 
  Clearances are in accordance with local installation codes and 
the requirements of the gas supplier. (Dégagement conforme 
aux codes d’installation locaux et aux exigences du foumisseur 
de gaz.) 
Canadian Installations  
(CSA B149.1) 
U.S. Installations 
(ANSI Z223.1 /NFPA 54)  
Ref 
Description  Direct Vent (Indoor Unit)  Direct Vent (Indoor Unit) 
A 
Clearance above grade, veranda, porch, deck, or balcony 
12 in. (30 cm)  12 in. (30 cm) 
B 
Clearance to window or door that may be opened 
36 in. (91 cm)  12 in. (30 cm) 
C 
Clearance to permanently closed window 
*  * 
D 
Vertical clearance to ventilated soffit, located above the terminal 
within a horizontal distance of 2 ft (61 cm) from the center line of 
the terminal 
*  * 
E 
Clearance to unventilated soffit 
*  * 
F 
Clearance to outside corner 
*  * 
G 
Clearance to inside corner 
*  * 
H 
Clearance to each side of center line extended above meter/
regulator assembly 
*  * 
I  Clearance to service regulator vent outlet 
Above a regulator within 3 ft 
(91 cm) horizontally of the 
vertical center line of the 
regulator vent outlet to a 
maximum vertical distance of 15 
ft (4 m) 
* 
J 
Clearance to non-mechanical air supply inlet to building or the 
combustion air inlet to any other appliance 
36 in. (91 cm)  12 in. (30 cm) 
K  Clearance to a mechanical air supply inlet  6 ft (1.83 m) 
3 ft (91 cm) above if within  
10 ft (3 m) horizontally 
L 
Clearance above paved sidewalk or paved driveway located on 
public property 
7 ft (2.13 m) [1]  * 
M  Clearance under veranda, porch, deck, or balcony   12 in. (30 cm) [2]   * 