Installation Guide
Polypropylene (PP) Common Venting Installation Instructions            22 
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.  
Combuson Air Requirements  
Combuson air provided to the system should not 
be taken from any area of the structure that may 
produce a negave pressure (i.e. exhaust fans, pow-
ered venlaon fans). 
NOTICE 
Using Indoor Air For Combuson 
When using air from other room(s) in the building, the 
total volume of the room(s) must be of adequate 
volume (Greater than 50 cubic feet per 1000 Btu/hr). 
Each Combuson air opening must have at least one 
square inch of free area for each 1000 Btuh, but not 
less than 100 square inches each. 
When communicang directly with the outdoors 
through horizontal ducts, each opening shall have a 
minimum free area of 1 in
2
/2000 Btu/hr (1100 mm
2
/
kW) of total input rang of all appliances in the 
conned space.     
Note: If ducts are used, the cross seconal area of the 
duct must be greater than or equal to the required 
free area of the openings to which they are 
connected. 
When communicang indirectly with the outdoors 
through vercal ducts, each opening shall have a 
minimum free area of 1 in
2
/4000 Btu/hr (550 mm
2
/
kW) of total input rang of all appliances in the 
conned space. Combuson air to the appliance can 
be provided from a well venlated ac or crawl 
space. 
 WARNING 
TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH 
DUE TO ASPHYXIATION, 
COMMON VENTING WITH OTHER MANUFACTURER’S 
INDUCED DRAFT APPLIANCES IS NOT ALLOWED. 
□ Verify proper clearances around the vents. 
□ Ensure that the Combuson Air Requirements 
are followed that will provide sucient 
combuson air for the appliance. 
□ Ensure approved venng components have been 
used. 
□ All horizontal vent runs must be sloped up away 
from the water heater a minimum of 1/4”(6 mm) 
per foot. 
□ Verify that there is adequate combuson air. 
□ Installaon complies with  
Naonal Fuel Gas 
Code, ANSI Z223.1/NFPA 54
 as well as local and 
state regulaons therein. 
Checklist for Combuson Air and 
Venng Requirements  
(Be sure to also maintain 12” above grade or  
ancipated snow level)   
Vent terminaon per ANSI Z223.1/NFPA 54. For 
clearances not specied in ANSI Z223.1/NFPA 54, 
clearances are in accordance with local  
installaon codes and the requirements of the gas 
supplier. 
Exhaust 










