Installation Guide
Polypropylene (PP) Common Venting Installation Instructions            21 
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.  
Louvers and Grills 
When sizing the permanent opening consideraon 
must be taken for the design of the louvers or grills to 
maintain the required free area required for all gas 
ulizing equipment in the space. If the free area of the 
louver or grill design is not available, assume wood 
louvers will have 25% free area and metal louvers or 
grills will have 75% free area. Under no circumstance 
should the louver, grill or screen have openings 
smaller than 1/4”. 
Example: 
Wood: 10 in x 12 in x 0.25 = 30 in
2 
Metal: 10 in x 12 in x 0.75 = 90 in
2
Locaon 
To maintain proper circulaon of combuson air two 
permanent openings (one upper, one lower) must be 
posioned in conned spaces. The upper shall be 
within 12” of the top of the conned space and the 
lower opening shall be within 12” of the boom of the 
conned space. Openings must be posioned as to 
never be obstructed. 
Using Outdoor Air For Combuson 
Outdoor air can be provided to a conned space 
through two permanent openings, one commencing 
within 12 in. (300mm) of the top and one commencing 
within 12” (300mm) of the boom, of the conned 
space. The openings shall communicate to the outside 
by one of two ways. 
Vent terminaon per ANSI Z223.1/NFPA 54. For 
clearances not specied in ANSI Z223.1/NFPA 54, 
clearances are in accordance with local installaon 
codes and the requirements of the gas supplier. 
(Be sure to also maintain 12” above grade or 
ancipated snow level)   
Combuson Air Requirements  
Exhaust 