Installation Guide
Polypropylene (PP) Common Venting Installation Instructions            19 
Copyright © 2018 Rinnai America Corporation. All Rights Reserved.  
Horizontal Terminaon Clearances 
This appliance along with the Common Vent System is cered with the 3”, 4”, 6” Wall Terminaon mounted 
in the orientaon shown below. 
The exhaust and combuson air terminaons must follow these clearances: 
•  12 inch minimum vercally from boom of combuson air terminaon to ground or ancipated snow 
line. 
•  12 inch minimum from edge of exhaust terminaon to edge of combuson air terminaon. 
There should be a minimum of 36 inch between exhaust terminaons in mulple common vent installaons. 
Refer to the Rinnai installaon and operaon manual for maximum vent lengths based on the vent diameter 
installed. 
NOTE: During colder weather when the exhaust 
temperature is much hoer than the outside air, the 
exhaust fumes will condense, producing water vapor. 
As a result a plume of water vapor may be seen leaving 
the exhaust. 
EXHAUST 
VENT 
COMBUSTION 
AIR VENT 
Vent Size  Separaon Distance 
3”, 4”, 6”  12” Minimum 
•  MINIMUM 12”  
From Exhaust Vent to Combustion Air Vent: 
•  Minimum 12”  
COMBUSTION AIR IS NOT ALLOWED 
IN THE SHADED AREA 
Combustion 
Air Vent 
Combustion 
Air Vent 
Combustion 
Air Vent 
Combustion 
Air Vent 
Combustion 
Air Vent 
Min 12” above grade or 
anticipated snow level 
Exhaust 
Vent 